Digital Display
A
3-Digit Display: Shows measured or calculated values such as Amperage, Kilowatts,
Voltage and Power Unbalance Percentage.
B
Arrow Buttons: Scroll through indicated Input, Bank, Power, Load Balance and Display
Brightness options using these buttons. A long press of the up or down arrow buttons allows
the user to skip to the next sequential measurement category.
C
Mode Button: When a menu option is selected using the Arrow Buttons, the Mode Button
scrolls through the sub-options within each category. Sub-options are shown by the
Indicator LEDs.
D
Indicator LEDs: Lit LED indicates which value is being displayed on the 3-digit screen.
Amps (A): When selected, the load on the selected Input Phase (L#) or
Load Bank (B#) is displayed in amps.
Wattage (kW): When selected, the load on the selected Load Bank (B#) or
Total Output Power (OP) is displayed in kW.
Voltage (V): Input Phase (L#) or Load Bank (B#) voltage is displayed.
Unbalanced Load (%UB): When lit, the display shows the unbalanced load
percentage deviance from the average measured value. A value that is zero or closest
to zero is desirable.
E
2-Digit Display: This display indicates which Input Phase (L#), Load Unbalance (UB),
Load Bank (B#) or Output Power (OP) option is selected.
Button Response Definitions:
Switch
Up
Pushbutton
Down
Pushbutton
Mode
Pushbutton
14-08-206-93338E.indb 5
E
Action
Control Function
Depress ½ sec
Sequentially, moves up one selection in the menu.
Depress 3 sec
Advances up to the next measurement category.
Depress ½ sec
Sequentially, moves down one selection in the menu.
Depress 3 sec
Advances down to the next measurement category.
Depress ½ sec
Displays available options for a given measurement category.
Depress 3 sec
Selects the chosen available option for a given configuration category.
C
D
B
5
A
10/9/2014 11:31:51 AM