Master setup
1. Supply power to the IPFC master.
2. If not yet completed, perform the initial configuration as described on chapter 6.2
3. Initial view is shown:
4. Scroll until:
5. Press ENT
6. Press ENT
7. Insert password (default 001).
8. Scroll until:
9. Set ON
10. Set:
Address
XX
Alternance
ON/OFF
Start delay AUX
t = XX [s]
11. Press STOP (red button)
12. Press STOP again
Inv: ON/OFF Mot: ON/OFF
p_mis=XX.X [bar]
Menù
ENT to access
MENU'
Control. param.
Combo
ON/OFF
IPFC's address in parallel operation.
00 : IPFC master
00
Function to allow alternating between the IPFCs connected in parallel in order to
allow equal use of each pump in the group; in this way Master will reorganize the
OFF
starting priority of the pumps by checking the life of each of them.
Delay time with which the slaves start after the variable speed pump has reached
the maximum frequency and the pressure value has fallen below set value – delta
0
control
35