5. Commissioning, operation
Menu
Description
item
AVG1/AVG2
Damping (switching output 1 / 2)
EN
AVG3
Damping (analogue signal)
UNIT
Unit switching
0SET
Adjust zero point / Perform "Autozero"
(max. 3 % of span)
DISM
Display value in display mode
DISU
Refresh rate (digital indicator)
DISR
Rotate the indication by 180° (digital
indicator)
DRES
Resolution (digital indicator)
RHL
Clear memory (Min/Max system pressure)
PAS
Password entry
TAG
Measuring instrument name (TAG)
16
Parameter
0.00 ... 65.00 s
0.00 ... 65.00 s
BAR, mBAR, MPA, KPA, PSI, KGcm (kg/cm²),
%
Yes / No
ACT = current system pressure
LOW, HIGH = Min/Max system pressure
OFF = display off
SP1/FH1 = set switching value
RP1/FL1 = set switching value
SP2/FH2 = set switching value
RP2/FL2 = set switching value
1, 2, 5, 10 updates/second
Yes / No
OPT = optimised (stable measurement value
on display with rounding factors for the last
digit, optimised to the measuring range)
FULL = maximum (finest resolution, if required
for a stable measurement value on display, a
damping must be set for the digital indicator)
Yes / No
0000 = no password
Password input digit by digit
32 selectable characters (A-Z ‚0 ... 9; -
‚SPACE)
(2 spaces in sequence terminate the input and
lead to the deletion of this and the underlying
characters)
WIKA operating instructions pressure switch, model PSD-4
Factory setting
0.00 s
0.00 s
Order-related
ACT
5
OPT
0000
without