9.2 PIPELINE LENGTH INCREASE
SPIKA MS 500 is filled with the necessary quantity of R404A for no more than 16.4 ft (5 m) pipeline length. To increase
this length, add 2.82 oz. (80 g) R404A per 16.4 ft (5 m). The maximum pipeline length increase will be 82 ft (25 m).
SPIKA MS 1000 is filled with the necessary quantity of R404A for no more than 16.4ft (5 m) pipelines length. To
increase this length, add 8.5 oz. (240 g) R404A per 16.4 ft (5 m). The maximum pipeline length increase will be 82 ft
(25 m).
9.3 FACTORY SETTINGS
•
Head pressure regulator: 10 bar.
•
Pressure switch protection: 30 bar.
9.4 ELECTRICAL CONNECTION
Machines are non-cord-connected and the power line has to be connected at the rear of them. All the power requirements
are on the data plate. Always use qualified personnel.
The power supply for the machine and the remote condenser are independent. This means no wiring between them is
necessary.
Follow all applicable local, state and national codes
Image 2 shows how to connect the remote condenser.
ICE MAKING HEAD
Figure 2. Remote condenser connection
PIPE SIZE AND FITTINGS
LIQUID LINE
HEAD FITTING
CONDENSER FITTING
DISCHARGE LINE
HEAD FITTING
CONDENSER FITTING
SAE FLARE
LIQUID
ODS
DISCHARGE
SAE FLARE
DISCHARGE
ODS
LIQUID
REMOTE CONDENSER
MS 1000R
5/16'' COOPER PIPE
1/4'' COOPER PIPE
3/8'' SAE FLARE
3/8'' SAE FLARE
5/16'' ODS
1/2'' COOPER PIPE
3/8'' COOPER PIPE
1/2'' SAE FLARE
3/8'' SAE FLARE
1/2'' ODS
7
USER MANUAL SPIKA
MS 500R
1/4'' ODS
3/8'' ODS