User and installation manual HNS-T1
Selecting the steam generator output for the steam room
You can estimate the power requirement using the formula below.
3
Volume (m
) x K1 x K2 = Power requirement (kW)
Forced ventilation
No ventilation
Acrylic wall
Light wall: board + tile
Heavy wall: stone, concrete + tile
Very heavy wall: stone, concrete + tile
In heavy built steam rooms, it is recommended to use e.g. electric heating cable for warming the seats,
walls and floors.
Output
Light struc-
ture, acryl-
ic, tem-
pered glass
kW
No A/C
3,4
2 – 7 m³
4,7
3 – 8 m³
6,0
4 – 13 m³
7,7
6 – 15 m³
9,5
9 – 17 m³
12,0
12 – 24 m³
14,0
18 – 30 m³
Table for selecting a steam generator based on the steam room volume and wall materials.
All manuals and user guides at all-guides.com
K1 = 0.75
K1 = 0.52
K2 = 1.00
K2 = 1.25
K2 = 1.50
K2 = 2.00
Light
board
wall
+ tile
Air condi-
No A/C
Air condi-
tioned
tioned
2 – 6 m³
2 – 6 m³
2 – 5 m³
3 – 7 m³
3 – 7 m³
2 – 6 m³
4 – 9 m³
4 – 8 m³
3 – 7 m³
6 – 11 m³
6 – 10 m³
5 – 9 m³
9 – 13 m³
9 – 14 m³
8 – 13 m³
11 – 18 m³
11 – 20
9 – 16 m³
14 – 22 m³
14 – 24
12 – 18 m³
Heavy wall,
Steam
concrete,
kg / h
stone
No A/C
Air condi-
tioned
2 – 5 m³
2 – 4 m³
5
2 – 6 m³
2 – 5 m³
6
3 – 7 m³
3 – 6 m³
8
5 – 9 m³
4 – 8 m³
10
7 – 11 m
6 – 9 m
13
9 – 16 m³
8 – 12 m³
16
11 – 17 m³
10 – 14 m³
19
11