LG ACHH Serie Manual Del Propietario Y De Instalación página 135

2. Hot Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (Mode Heat)
500Ω
Volt [V]
[mA]
0.0
0.0
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
2.0
4.0
2.2
4.4
2.4
4.8
2.6
5.2
2.8
5.6
3.0
6.0
3.2
6.4
3.4
6.8
3.6
7.2
3.8
7.6
4.0
8.0
4.2
8.4
4.4
8.8
4.6
9.2
4.8
9.6
5.0
10.0
5.2
10.4
5.4
10.8
5.6
11.2
5.8
11.6
6.0
12.0
6.2
12.4
6.4
12.8
6.6
13.2
6.8
13.6
7.0
14.0
Heat Set Point
(30 ~ 70) [°C]
No Control
(Disconnected)
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Heat Set Point
(86 ~ 158) [°F]
No Control
(Disconnected)
86
87.8
89.6
91.4
93.2
95
96.8
98.6
100.4
102.2
104
105.8
107.6
109.4
111.2
113
114.8
116.6
118.4
120.2
122
123.8
125.6
127.4
129.2
131