APÉNDICE
134
• Remote desired temperature contact point table
1. Chilled Water Set Point (2 ~ 10 V, 4 ~ 20 mA)
: UI3 (Mode Cool)
500Ω
Volt [V]
[mA]
0.0
0.0
0.2
0.4
0.4
0.8
0.6
1.2
0.8
1.6
1.0
2.0
1.2
2.4
1.4
2.8
1.6
3.2
1.8
3.6
3.0
6.0
3.2
6.4
3.4
6.8
3.6
7.2
3.8
7.6
4.0
8.0
4.2
8.4
4.4
8.8
4.6
9.2
4.8
9.6
5.0
10.0
5.2
10.4
5.4
10.8
5.6
11.2
5.8
11.6
6.0
12.0
6.2
12.4
6.4
12.8
6.6
13.2
6.8
13.6
7.0
14.0
7.2
14.4
7.4
14.8
7.6
15.2
7.8
15.6
8.0
16.0
8.2
16.4
8.4
16.8
8.6
17.2
8.8
17.6
9.0
18.0
Cool Set Point
(-10 ~ 20) [°C]
No Control (Disconnect-
ed)
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Cool Set Point
(14 ~ 68) [°F]
No Control (Disconnect-
ed)
14
15.8
17.6
19.4
21.2
23
24.8
26.6
28.4
30.2
32
33.8
35.6
37.4
39.2
41
42.8
44.6
46.4
48.2
50
51.8
53.6
55.4
57.2
59
60.8
62.6
64.4
66.2
68
Etc
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)
(Low Temp. Type)