Troubleshooting

If the room temperature is less than 17 °C, the cooling mode must be
switched on manually. This manual operation is only envisaged for
testing and emergency situations.
▶ Otherwise, always use the remote control.
To switch on the cooling mode manually:
▶ Switch off the indoor unit.
▶ Press the key for the manual cooling mode twice with a thin object
( Fig. 23).
▶ Press the Mode key on the remote control to exit cooling mode when
it has been set manually.
In a system with multi-split air conditioner, manual operation is not
possible.
4.3

Handover to the user

▶ When the system has been set up, hand over the installation manual
to the customer.
Fault code
Possible Cause
EC 07
Fan speed of outdoor unit outside the normal range
EC 51
Faulty parameter in the EEPROM of the outdoor unit
EC 52
Temperature sensor error at T3 (condenser coil)
EC 53
Temperature sensor error at T4 (outside temperature)
EC 54
Temperature sensor error at TP (compressor discharge pipe)
EC 56
Temperature sensor error at T2B (outlet of evaporator coil; only multi-split air conditioner)
EH 0A
Faulty parameter in the EEPROM of the indoor unit
EH 00
EH 0b
Communication error between main PCB of indoor unit and display
EH 02
Fault when detecting the zero-crossing signal
EH 03
Fan speed of indoor unit outside the normal range
EH 60
Temperature sensor error at T1 (room temperature)
EH 61
Temperature sensor error at T2 (centre of evaporator coil)
1)
EL 0C
Insufficient or escaping refrigerant or temperature sensor error at T2
EL 01
Communication error between IDU and ODU
PC 00
Fault at IPM module or IGBT overcurrent protection
PC 01
Over- or undervoltage protection
PC 02
Temperature protection at compressor or overheating protection at IPM module or pressure relief device
PC 03
Low pressure protection
PC 04
Inverter compressor module error
PC 08
Protection against current overload
PC 40
Communication fault between main PCB of outdoor unit and main PCB of compressor drive
−−
Conflicting operating mode of indoor units; operating mode of indoor units and outdoor unit must correspond.
1) Leak detection not active, if in a system with multi-split air conditioner.
Table 70
5.2

Faults not indicated

Fault
The output of the indoor unit is too low.
50
▶ Explain to the customer how to use the system, referring to the
operation manual.
▶ Advise the customer to carefully read the operation manual.
5
5.1
Risk to life from electric shock!
Touching live electrical parts can cause an electric shock.
▶ Before working on electrical parts, disconnect all phases of the
power supply (fuse/circuit breaker) and lock the isolator switch to
prevent unintentional reconnection.
If a fault occurs during operation, a fault code appears in the display
(e.g. EH 02).
If a fault is present for more than 10 minutes:
▶ Briefly interrupt the power supply and switch the indoor unit back on.
If a fault persists:
▶ Call customer service and provide the fault code and details of the
appliance.
Possible cause
Heat exchanger of the outdoor or indoor unit
contaminated or partially blocked.
Shortage of refrigerant
Troubleshooting

Faults with indication

WARNING
Remedy
▶ Clean heat exchanger of outdoor or indoor
unit.
▶ Check tightness of pipes, reseal if required.
▶ Refill refrigerant.