Configuring MODE 1
SELECT
MODE CONFIG
9
MODE CONFIG
MODE:1
6
9
9
MODE CONFIG
SETUP
MODE1 CONFIG
9
MODE1 CONFIG
MODE1 CONFIG
LOGIC:ALTERN.
MODE1 CONFIG
DRY LOGIC:COS
MODE1 CONFIG
COSFI REC:ON
MODE1 CONFIG
REC TIME:2m
MODE1 CONFIG
MAX REC T:60m
• Press the
• If MODE:1 appears on the display, press the
mode 1 configuration, otherwise press the
and change the mode.
• Press the
MODE:1
(from modes 1 to 6)
• Press the
• Press the
• Press the
• Enable (ON) or disable (OFF) input IN1
IN1:ON
• This input is used to start a single electric pump according to the alternating
logic
• Enable (ON) or disable (OFF) input IN2
IN2:ON
• This input is used to start the second electric pump according to the alter-
nating logic, or to start both electric pumps simultaneously
• If the system has two electric pumps, enable (ALTERN.) or disable (SIN-
GLE) the alternating logic.
• Set whether the dry running stop logic is based on the motor current read-
ing (CURR) or cosφ reading (COS)
• Enable (ON) or disable (OFF) automatic COSFI recovery when it is below
COSFI MIN (dry running)
• With COSFI RECOVERY, the control panel attempts to automatically recover
an electric pump that is in the dry running alarm state (COSFI read < COSFI
minimum)
• Recovery time for automatic deactivation of the dry running alarm.
• The control panel attempts automatic recovery after the set time, and then
doubles it on each subsequent cycle (e.g. 2 min, 4 min, 8 min ...), up to the
maximum recovery time (see the next parameter).
Default 2 min
• Maximum recovery time for automatic deactivation of the dry running
alarm.
• The control panel attempts automatic recovery up to the set maximum val-
ue (e.g. every 60 min).
Default 60 min
key to confirm the choice and enter the submenu.
or
key to select mode 1
key to confirm the choice of MODE:1
key to continue with the configuration
key to enter the mode 1 configuration submenu
Range 0-10 min
Range 0-120 min
key to continue and enter
key to enter the submenu
Step 1 min
Step 1 min
Continued
ENGLISH |
57