SELECT
PUMP2 CONFIG
9
SELECT
INOUT CONFIG
9
SELECT
MODE CONFIG
9
9
Electric pump no. 2 configuration (if any)
PUMP2 CONFIG
WIZARD
PUMP2 CONFIG
CURRENT:5.0A
PUMP2 CONFIG
CURR TOUT:7s
PUMP2 CONFIG
VOLT MIN
PUMP2 CONFIG
VOLT MAX
PUMP2 CONFIG
VOLT TOUT
PUMP2 CONFIG
COSFI MIN:0.50
PUMP2 CONFIG
COSFI TOUT:5s
PUMP2 CONFIG
CURR MIN
PUMP2 CONFIG
CURM TOUT
PUMP2 CONFIG
MOT PROT:OFF
PUMP2 CONFIG
DISABLE:OFF
Configure inputs and outputs
INOUT CONFIG
IN ALARM:ON
INOUT CONFIG
OUT ALARM:ON
INOUT CONFIG
LEVEL SENS:50
INOUT CONFIG
P.TYPE:4-20mA
INOUT CONFIG
P.RANGE:16bar
CUSTOMISED PRESET MODE configuration (mode 1 to 6)
MODE CONFIG
MODE:1
MODE CONFIG
SETUP
MODE CONFIG
MODE:2
MODE CONFIG
SETUP
...
...
Self-learn configuration (wizard)
Electric pump maximum current
Overcurrent trip delay
Minimum operating voltage
Maximum operating voltage
MAX/MIN voltage trip delay
Electric pump minimum cosφ
Dry running trip delay
Minimum operating current
Undercurrent trip delay
Motor thermal cut-out
Electric pump no. 2 enable/disable
External alarm input
External alarm output (NO/NC)
Level sensor percentage sensitivity
Pressure transducer type
Pressure transducer range
Mode 1 automatic operation
Configure mode 1 customised operation
Mode 2 automatic operation
Configure mode 2 customised operation
...
...
Continued
ENGLISH |
51