INSTALLATION INSTRUCTIONS
INDOOR CLEARANCES
(Appearance may vary)
This picture is for reference only. Your product may look different.
More than 4 inches
Wrap the insulation pipe with
bottom to top.
Cut thermal insulation pipe to an
appropriate length and wrap it with tape,
making sure that no gap is left in the
insulation pipe's cut line.
SALTWATER COAST INSTALL
• The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland
waterways. Please follow the installation instruction below if the unit installed from ½ mile to 5 miles away from the
salt water, including seacoasts and inland waterways.
• Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can
damage the outdoor unit.
Sea Breeze
Sea
• Construct a protection wall around it to block the sea breeze if you cannot avoid installing the outdoor unit by
the seashore.
• A protection wall should be constructed with a solid material to block the sea breeze.
The height and the width of the wall should be 1.5 times larger than the size of the
outdoor unit. Also, allow at least 28" (700mm) between the protection wall and the
outdoor unit for air circulation to ventilate.
• Install the outdoor unit in a place where water can drain.
• Contact Haier Ductless for assistance if the above conditions cannot be met.
LOW AMBIENT INSTALL
- If the outdoor unit is installed in a region that is affected by strong wind or snow accumulation, it is recommended
to install wind baffle or/and snow hood accessories. Corresponding snow hood and wind baffle model number can
be found in product catalog. The installation instructions can be found in the manual shipped with each accessory or
on-line at GEAppliancesairandwater.com.
14
More than 4 inches
ODU
ODU
Sea
Arrangement of
piping directions
Rear Left
Left
Below
Condensate
piping must have a
downward slope of
at least 1/4" per foot
for proper drainage.
Sea Breeze
Protection Walls
Sea Breeze
Sea
Rear Right
Right
ODU
ODU
ODU
31-5000564 Rev. 3