7.3

Fault table

Fault
Overflow valve
does not respond
Not liftable
Leak in the seating
Damage to the
inlet/outlet
Shock waves
Constantly blowing
off
Chattering
Inadequate
capacity
22
Operating instructions
Cause
Covers have not been
removed;
Test pressure too high;
Back pressure not taken into
account;
Pressure below 85% of the set
pressure;
Foreign bodies between cone
and seating, contaminated
medium;
Seating damaged;
Cone seal damaged;
Overflow valve has fluttered;
Transport damage;
Wrong connecting thread /
tightening torque too high;
Impermissible forces such as
bending or torsional forces are
being transmitted;
Overflow valve not fitted at the
highest point;
water not drained correctly or
at all;
Spring corroded by
impermissible medium and
broken;
System pressure too high
Seal damaged;
Pressure drop in the inlet line
>3%;
Seals for inlet and outlet
connector too small or not
installed centrally;
overflow valves are too highly
rated;
Outlet line too long or diameter
too small;
Inlet or outlet connector too
small;
Back pressure higher than 3%;
overflow valves incorrectly
configured for the plant
conditions;
Overflow valves not being used
in accordance with the
applicable regulations;
Phone +49 4531 509-0
Remedy
Remove covers.
Replace the overflow valve.
Replace the overflow valve.
Lifting in the range ≥85 % of the set
pressure without aids.
Remove foreign bodies by briefly
lifting / flush the system or replace
the overflow valve.
Replace the overflow valve.
Replace the overflow valve.
See "Chattering".
Replace the overflow valve.
Replace the overflow valve.
Install stress-free.
Install the overflow valve at the
highest point.
Attach water drain according to
regulations.
Replace the overflow valve.
Replace the overflow valve.
Replace the overflow valve.
Reduce resistance through chamfer
or radius in the connecting socket;
choose a larger one if necessary.
Shorter inlet line.
Incorrect overflow valve, replace it.
Change conditions.
Select smaller overflow valves.
Use a larger nominal diameter or a
back-pressure-compensating
stainless steel bellows. The max.
height is to be specified by the
manufacturer.
Dimensions must be larger than the
nominal inlet or outlet diameter.
Use back-pressure-compensating
stainless steel bellows. The max.
height is to be specified by the
manufacturer.
Re-dimension and replace the
overflow valve.
Change conditions.