Custom Code Setting; Switching The Upper Limit Of Cooling Temperature; Dip Switch Setting - Fujitsu AIRSTAGE AUXD18GALH Manual De Instalación

Ocultar thumbs Ver también para AIRSTAGE AUXD18GALH:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 50
Table A
Rotary Switch
Address
Setting
REF AD SW
Refrigerant
circuit
× 10
× 1
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD SW
0
1
Address
0
1
RC AD SW
8
9
Address
8
9
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically confi gured, you do not
need to confi gure them.
If confi guring manually, it is necessary to confi gure both the indoor unit and the remote
controller. For details, please refer to the remote controller manual.

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor
unit
Remote
controller
En-13
9371022260-01_IM.indb Sec1:13
9371022260-01_IM.indb Sec1:13
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
1
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
2
3
4
5
6
7
2
3
4
5
6
7
A
B
C
D
E
F
10
11
12
13
14
15
Code change
A
B
C
D
A
B
C
Custom code setting for indoor unit
Set the DIP switch SET 3 SW1, SW2, referring to the Table B.
× 1
0
1
2
3
4
5
6
7
8
ON
9
0
OFF
1
2
SW
.
.
.
Table B
3
DIP switch SET 3 SW1
DIP switch SET 3 SW2

7.3. Switching the upper limit of cooling temperature

This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
• Wired remote controller (2-wire type)
• Central remote controller
• Touch panel controller
• System controller
• Service tool
• Web monitoring tool

DIP switch setting

Set the DIP switch SET 4 SW3 referring to the Table C.
Table C
DIP switch SET 4 SW3
OFF (Factory setting)
ON
NOTE:
Please do not make a standard setup and an extension setup intermingled in remote
controller group.
D
DIP switch "SET 3"
SW
SW
SW
1
2
3
4
Custom code
A (Factory setting)
B
OFF
ON
OFF
OFF
ON
DIP switch
"SET4"
OFF
SW
SW
SW
SW
1
2
3
4
Cooling temperature setting range
Standard (18 to 30 °C)
Extension (18 to 32 °C)
C
D
OFF
ON
ON
ON