Refrigerant piping installation
3 Outside Units
Combination specification
Y branch
A
To outside unit
A
To branch piping or indoor unit
B
22
Outside Unit
Connecting
branch pipe
Don't cut the pipe less than
70mm
I.D28.58(1-1/8)
I.D28.58(1-1/8)
I.D19.05(3/4)
38
ARCNN20
(1-1/2)
I.D22.2(7/8)
I.D19.05(3/4)
I.D19.05(3/4)
I.D15.88(5/8)
75(2-15/16)
Don't cut the pipe less than
70mm
I.D28.58(1-1/8)
ARCNN30
45
(25/32)
I.D28.58(1-1/8)
I.D34.9(1-3/8)
B
Viewed from point A
in direction of arrow
Gas pipe
Blow nitrogen while
brazing
I.D9.52(3/8)
24
I.D28.58(1-1/8)
I.D34.9(1-3/8)
(31/32)
I.D12.7(1/2)
I.D31.8(1-1/4)
363(14-9/32)
473(18-5/8)
I.D22.2(7/8)
I.D38.1(1-1/2)
O.D28.58(1-1/8)
O.D34.9(1-3/8)
83(3-9/32)
115(4-17/32)
Blow nitrogen while
brazing
I.D15.88(5/8)
I.D34.9(1-3/8)
I.D 41.3(1-5/8)
24
(31/32)
I.D12.7(1/2)
I.D38.1(1-1/2)
370(14-9/16)
440(17-5/16)
I.D22.2(7/8)
I.D19.05(3/4)
O.D28.58(1-1/8)
115(4-17/32)
downwards
Within +/- 10
Within 3
[mm(inch)]
Liquid pipe
I.D12.7(1/2)
I.D19.05(3/4)
I.D12.7(1/2)
I.D15.88(5/8)
331(13-1/32)
401(15-25/32)
I.D19.05(3/4)
I.D22.2(7/8)
I.D9.52(3/8)
O.D12.7(1/2)
80(3-5/32)
73(2-7/8)
I.D12.7(1/2)
I.D19.05(3/4)
I.D22.2(7/8)
289(11-3/8)
I.D19.05(3/4)
397(15-5/8)
I.D9.52(3/8)
O.D12.7(1/2)
73(2-7/8)
Facing
Facing
upwards
Within 3