Operation; Choice Of Nozzles; Pump Pressure; Adjustment Of The Air Damper Motor - Riello PRESS 60 N/ECO Instrucciones De Instalación, Uso Y Mantenimiento

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

4.

OPERATION

4.1

CHOICE OF NOZZLES

Recommended nozzle:
- Monarch F 80 H0.
4.2

PUMP PRESSURE

Recommended pressure:
- Light oil: 20 bar
- Heavy oil: 25 bar
The flow rate of the nozzes indicated in the table are
nominal, obtained for a light oil having viscosity from 3 to 5°E
at 50° C pre-heated at 100°C. The actual flow rate may vary
by ± 5% against the rated flow rate.
if flow rate values between those indicated in the table are
required, it is possible to vary the pump pressure or arrange
the nozzles differently.
The pump leaves the factory set at 20 bar.
4.3
COMBUSTION HEAD ADJUSTMENT
Turn the screw A, fig. 2 to the set-point, shown in the diagram,
lines up with sleeve B, fig. 2.
Fig. 2
D2637
4.4

ADJUSTMENT OF THE AIR DAMPER MOTOR

STOP - Blue lever
This lever leaves the factory vertically positioned and corre-
sponds to the complete closure of the air damper.
A partial opening of the air damper might be obtained by
moving this lever leftwards (+ on the plate).
The new position of the air damper is detectable when the
burner is off.
Do not exceed the position of the orange lever for the 1
stage.
st
1
STAGE - Orange lever
The orange lever controls the air damper position for the first
flame, it is adjustable both for opening and closing.
nd
2
STAGE - Red and black levers
The red lever controls the air damper position for the second
flame, it is adjustable both for closing and opening.
The black lever controls the opening of the second oil valve
and it must always anticipate - for a bit - the red lever, but
never the orange one.
6202
B
Set-point 4
A
6
Nozzle
GPH (45° - 60°)
2.50 + 2.50
3.00 + 3.00
3.50 + 3.50
4.00 + 4.00
4.50 + 4.50
5.00 + 5.00
kg/h
Black lever
Red lever
st
Orange lever
Blue lever
Opening +
GB
20 bar
25 bar
kg/h
kg/h
30.00
34.00
36.00
40,60
42.00
47,40
48.00
54,20
54.00
61.00
60.00
D2693
Set-point
D2638
– Closure
Tabla de contenido
loading

Este manual también es adecuado para:

34350813435082

Tabla de contenido