Operations
This section explains how to use your Tripp Lite Online UPS System, including front-panel LCD operation, operating modes, UPS startup and
shutdown, transferring between modes, setting power strategy, and configuring bypass settings, load segments and battery settings.
LCD Front Panel Display and Controls
A 5-button graphical LCD screen with additional LED indicators on the front of the UPS that provides information on UPS status, load level
information, event information, measurements, settings and a wide variety of UPS configuration and power strategy options.
AC Output LED (Green)
AC Input LED (Green)
LCD Screen
Escape
Page Up/Page Down
LED Front Panel Indicators
There are 4 LEDs above the front panel LCD screen that offer information on AC INPUT, BYPASS, AC OUTPUT, BATTERY MODE and UPS
FAULT status.
AC INPUT indicator
On
AC input is available AND AC input is WITHIN the configured ECONOMY / BYPASS mode range.
When this LED is ON SOLID, AC input is of adequate quality for UPS operation in BYPASS or ECONOMY MODE.
Flashing AC input is available AND AC input is OUTSIDE the configured BYPASS mode range.
When this LED is ON FLASHING, AC input is not of adequate voltage or frequency for UPS operation in BYPASS or
ECONOMY MODE.
Off
AC input is NOT available.
When this LED is OFF, AC input is not available.
AC OUTPUT indicator
210
On
UPS AC output is ON
UPS output is available at the UPS output receptacles.
Off
UPS AC output is OFF
UPS AC output is not available.
BATTERY MODE indicator
On
UPS is running in battery mode
3000
UPS batteries are discharging as the UPS runs in battery mode. Also lights momentarily during self-test operation.
Flashing UPS is running in battery mode - Low battery warning
3000
UPS batteries are discharging as the UPS runs in BATTERY mode and are becoming low. The indicator will flash at
2-second intervals to report LOW BATTERY and 0.5-second intervals to report BATTERIES ARE NEAR FULLY
DISCHARGED and the UPS is near shutdown.
UPS FAULT indicator
3000
On
UPS is experiencing a pre-defined fault state
3000
See front panel display for explanation of error state or code information. See on-screen instructions and manual
for troubleshooting tips.
Off
Normal
UPS is not reporting fault conditions when this indicator is OFF.
3000
3000
3000
210
3000
14
Battery Mode LED (Yellow)
Fault LED (Red)
On/Off
Enter