Window Function - WIKA FSD-3 Manual De Instrucciones

Detector de caudal
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation

Window function

The window function allows for the control of a defined range.
When the flow rate is between window high (FH) and window low (FL), the output
switches on.
Contact normally open (FNO): Active
Contact normally closed (FNC): Inactive
When the flow rate is outside window high (FH) and window low (FL), the output
does not switch on.
Contact normally open (FNO): Inactive
Contact normally closed (FNC): Active
Delay times (0 ... 50 s)
This makes it possible to filter out unwanted flow peaks of a short duration or
high frequency (damping).
The flow rate must be present for at least a certain pre-set time for the output to
switch on. The output does not immediately change its status when it reaches the
switching event (SP), but rather only after the pre-set delay time (DS).
If the switching event is no longer present after the delay time, the switching
output does not change.
The output only switches back when the flow rate has fallen down to the reset
point (RP) and stays at or below the reset point (RP) for at least the pre-set delay
time (DR).
If the switching event is no longer present after the delay time, the switching
output does not change.
WIKA operating instructions flow switch, model FSD-3
Fig.: Window function
Fig.: Delay times
EN
21

Hide quick links:

Tabla de contenido
loading

Tabla de contenido