11 DIMENSIONAL DRAWINGS (mm)

P1
P4
P3
164,0
P5
P2
E1 E2 1 2 7 6

12 IDENTIFICATION OF CONNECTION TERMINALS

E1: Sensing Voltage (160 up to 300Vac).
E2: Voltage (320 up to 600Vca).
3: Power supply.
E3/4: Sensing Voltage.
1¹: Connection for pole S1 of the CT, ratio In/5
2¹: Connection for pole S2 of the CT, ratio In/5
6 e 7: Connection for potentiometer 5K/3W.
F+, F-: Connection for generator field.
J1: Jumper 50/60Hz (J1 open = 50Hz – closed = 60Hz).
A²: Analog input voltage – 9 Vdc.
B²: Analog input voltage + 9 Vdc.
1
Available only for models TH4.
² Only for models TH4 E and TH4 PE.

13 DIAGRAM FOR TEST WITHOUT GENERATOR

Below is the diagram for regulator connection on the bench where the equipment operation may be verified before connection to
the generator.
Material required:
1 - Small screwdriver;
1 - Incandescent lamp;
1 - Lamp socket;
1 - Bipolar breaker (5A recommended);
1 - Extension cable;
1 - Plug 110V or 220V*.
* For voltage 110V, select refeeding jumper class "A";
* For voltage 220V, select refeeding jumper class "C";
NOTE
1. After performance of such steps as per the procedure the equipment must be sent for evaluation by
GRAMEYER technical support.
1º. Mount circuit as per diagram below;
2º. With small screwdriver, turn trimpots Vad and U/F counter-clockwise until the end of stroke;
18
|
Automatic Voltage Regulator - GRT7-TH4
Overview
115,0
50Hz
60Hz
100,0
F+
F- 3
E3/4
145,0
A
.
A
.
Front view
39,0
E1 E2
1
2
7
6
F+
F-
Fixing hole detail
3
E3/4