conform to local standard codes. The installation must conform to local codes, or in the absence of local
codes, with the standard for the storage and handling of liquid petroleum gases. A dented, rusted or
damaged tank may be hazardous and should be checked by your tank supplier. Never use a tank with a
damaged valve connection.
LEAKAGE TEST
Gas connections on the heater are leak tested at the factory prior to shipment. A complete gas tightness
check must be performed at the installation site due to possible mishandling in shipment or excessive
pressure being applied to the heater. Make a soap solution of one part liquid detergent and one part water.
The soap solution can be applied with a spray bottle, brush or rag. Soap bubbles will appear in case of a
leak. The heater must be checked with a full cylinder. Make sure the safety control valve is in the OFF
position. Turn the gas supply ON. In case of a leak, turn off the gas supply. Tighten any leaking fittings, then
turn the gas supply on and recheck. Never leak test while smoking.
OPERATION AND STORAGE
TO TURN ON THE HEATER
1. Turn on the valve on the gas supply cylinder completely.
2. Press and turn the variable control knob to PILOT position (counter-clockwise 90º).
3. Press down the variable control knob and hold for 60 seconds. While holding down the variable control
knob, press the igniter button several times until pilot flame lights. Release the variable control knob after
the pilot flame lights. Note: If a new tank has just been connected, please allow at least one minute for the
air in the gas pipeline to purge out through the pilot hole. Variable control knob can be released after the
pilot flame lights. If the pilot flame does not light or it goes out, repeat step 3.
4. After the pilot flame lights, turn the variable control knob to maximum position and leave it there for 5
minutes or more before turning the knob to desired temperature position.
Warning: check that no broken on the glass is found before operation
TO TURN OFF THE HEATER
1. Turn the variable control knob to PILOT position.
2. Press and turn the variable control knob to OFF position
Off: Turn off.
Max: Maximum temperature
Min: Minimum temperature
3. TURN OFF THE VALVE ON THE GAS SUPPLY CYLINDER COMPLETELY.
17
|