3. CONNECTING THE REMOTE CONTROL CABLE
TO MONO BLOC UNIT
Be sure to turn off the main power before installing and connecting
the remote control. Otherwise, it will cause the electrical shock.
1. Remove the cabinet front plate.
2. Connect the remote control cable with the provided connector as
shown in below illustration. (Refer wiring diagram for detail.)
3. Guide the remote control cable through the clamper and Bushing
7.
(Refer illustration "How to connect Remote Control to Provided
Connector" for detail.)
4. Reinstall the cabinet front plate after connection complete.
Remove this dummy connector
cap first, before plug in
PCB
Provided
Connector
Connect the wired remote
control cable with the connector
provided here
How to connect Remote Control to Provided Connector
5
CHECKING AND TEST RUN
PROCEDURES
Be sure to switch off all the power supply before performing each of
the below action.
Remove The Cabinet Front Plate 8
(1) Remove the 5 mounting screws
as shown in the illustration.
(2) Slide the cabinet front plate 8
downward to release the pawls.
Then, pull it toward front to
remove it.
Remove The Cabinet Top Plate 9
(1) Remove the 11 mounting screws
as shown in the illustration.
(2) Lift the cabinet top plate 9
upward to remove it.
8
WARNING
Remote
Control
Connector
Plug in firmly
Remote
control
Clamp the wired
remote control cable
with clamper.
Wired remote
control cable
Bind the wired
remote control
cable and all
power supply
cords to the tube
with band strap
(fi eld supply)
Bushing 7
Apply cut
WARNING
8
Mounting screws
Mounting
screws
9
RESET OVERLOAD PROTECTOR 0
Overload Protector 0 serves
the safety purpose to prevent
the water over heating. When
the Overload Protector 0 trip
at high water temperature,
take below steps to reset it.
1. Take out OLP Cover.
2. Use a test pen to push
the centre button gently
in order to reset the
Overload protector 0.
3. Fix the OLP Cover to the original fi xing condition.
CHECK WATER PRESSURE
Water pressure should not lower than 0.05 MPa (with inspects the
pressure gauge). If necessary add tap water into tank unit. Refer to
tank unit installation instruction for details on how to add water.
CHECK PRESSURE RELIEF VALVE 2
•
Take out the cover c with remove the
mounting screw for access to the pressure
relief valve 2.
•
Check for correction operation of pressure
relief valve by turn up the lever to become
horizontal (Refer to fi gure of "Pressure
relief valve 2")
•
If you do not hear a clacking sound (due
to water drainage), contact your local
authorized dealer.
•
Turn down the lever after checking
finish. In case the water keeps
drained out from the unit, switch off
the system, and then contact your
local authorized dealer.
•
Reinstall the cover c with tighten
the mounting screws properly, if the
pressure relief valve 2 is functioning
normal.
HOW TO ADJUST WATER FLOW RATE
Before adjust the water fl ow rate, make sure that the total water
volume in the installation is 50 litres minimum for heating side. The
default setting is SPEED 6 for WH-MXC16G9E8. Please ensure
the minimum fl ow rate is not less than 13 l/min and not more than
50 l/min.
The available external static pressure (kPa) in function of the water
fl ow rate (l/min) is shown in the P-Q graph. Depend on the hydraulic
system pressure loss and type, the water fl ow rate can be adjusted
by remote control.
1. When the Air-to-Water Heatpump is in stop operation, press
SERVICE button for 5 seconds.
2. Press / button to select menu S02 (PUMP SPEED ADJUST
MODE) and press SET button to confi rm the menu.
3. Press SELECT button then press / button to change pump
speed and press SET button to confi rm the pump speed.
4. Press OFF/ON button to exit PUMP SPEED ADJUST MODE.
During PUMP SPEED ADJUST MODE, we can select AIR PURGE
function by pressing FORCE button.
Mounting
In AIR PURGE function, the pump will operate ON and OFF for 10
screws
minutes to purge the air in the hydraulic system. Press again the
FORCE button to exit AIR PURGE function. PUMP SPEED ADJUST
MODE will stop operation.
130
120
110
100
90
80
70
60
50
40
30
20
10
0
How to reset Overload protector 0
*(0.1 MPa = 1 bar)
Lever
Turn up
Pressure relief valve 2
7
6
5
4
3
2
1
0
10
13
20
30
40
50
WATER FLOW RATE (L/min)
Use test pen to
push this button
for reset Overload
protector 0.
13