Honeywell TR21 Manual Del Usuario página 7

Ocultar thumbs Ver también para TR21:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Table 7. Wall Module Operation.
Pushbutton Held Down
Controller Model
0 to 1 second
No override
1 to 4 seconds
Timed occupied
override
4 to 7 seconds
Unoccupied override Single blink per second
Longer than 7 seconds
No override
not applicable
Continuous occupied
override
a
Remote function, which is generated from the network.
RESET
NOT ASSIGNED
(LED OFF)
PRESS FOR ONE
PRESS FOR
TO FOUR SECONDS
LESS THAN
ONE SECOND
OVERRIDE
OCCUPIED
(LED ON)
PRESS FOR FOUR
TO SEVEN SECONDS
PRESS FOR
UNOCCUPIED
LESS THAN
(LED BLINK)
ONE SECOND
Fig. 5. Override pushbutton operation.
When Used With Excel 600/500/100/80 Controllers:
The application engineer/programmer can program the
override (bypass) and LED to operate in any manner desired.
The override (bypass) input is a dry contact, normally open,
momentary digital input when the wall module does not have a
fan switch. When a fan speed switch (basically a series of
resistances based on fan switch position) is present, the
override button is an analog input. See Table 9 for
resistances.
When Used With T7350 Thermostat:
TR21, TR21-A, TR21-H, TR22, TR23, and TR24 are the
models compatible with the T7350 thermostat. When using
with the T7350 thermostat be sure to use the relative +/- offset
knob only. The Celsius and Fahrenheit knobs will not work
properly with the T7350 Thermostat.
L
W
® is a registered trademark of Echelon® Corporation.
ON
ORKS
L
M
® and the LonMark Logo are trademarks of the LonMark Association.
ON
ARK
LED Status
Off
On
Off
Two blinks per second
a
BYPASS
TIMEOUT
PRESS FOR
MORE THAN
SEVEN SECONDS
TR21, TR22, TR23, AND TR24 WALL MODULES
TR22-F5, TR23-F3, and TR23-F5 Wall Module
Fan Switch
With the switch in the far left position (Auto), the fan
automatically runs at the speed determined by the controller
temperature control algorithm.
With the switch in the 0 position, the fan is off. Position 1 is fan
speed 1, etc.
The wall module fan speed switch overrides the temperature
control algorithm.
When Used With Excel 10 Controllers:
The Excel 10 Controllers (W7750, W7751, W7752, and
W7753) can be programmed so that the fan speed switch and
override button function the way that the application engineer/
programmer wants. See Table 8 for controller-programming
resistances. Switch 1 on Dip Switch S2 adds 10k Ohms
resistance when OPEN (for Excel 600-80 controllers) and
removes it when CLOSED (for Excel 10 controllers).
Table 8. Program Settings for Wall Modules with
Fan Switch using Excel 10 Controllers.
For Switch Position
Auto
0
1
2
3
Override button closed Closed circuit
M28145
When Used With Excel 600/500/100/80 Controllers:
Excel 600/500/100/80 Controllers can be programmed so that
the fan speed switch and override button function the way that
the application engineer/programmer wants. See Table 9 for
controller-programming resistances. Switch 1 on Dip Switch
S2 adds 10k Ohms resistance when OPEN (for Excel 600-80
controllers) and removes it when CLOSED (for Excel 10
controllers).
Table 9. Program Settings for Wall Modules with
Fan Switch using Excel 600/500/100/80 Controllers.
For Switch Position
Auto
0
1
2
3
Override button closed 10K ±100
7
Resistance (Ohms)
Comment
1861 ±119
Left most position
2686 ±127
Fan Off position
3866 ±139
304 ±130
460 ±146
Right most position
Resistance (Ohms)
Comment
11.861K ±119
Left most position
12.686K ±127
Fan Off position
13.866K ±139
13.04K ±130
14.60K ±146
Right most position
63-1321ES—06
Tabla de contenido
loading

Tabla de contenido