Honeywell NOTIFIER M710E-CZR Instrucciones De Instalación
Honeywell NOTIFIER M710E-CZR Instrucciones De Instalación

Honeywell NOTIFIER M710E-CZR Instrucciones De Instalación

Modulo monitor para zonas convencionales
Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Fig./Abb. 1
1:2 DIN
1:1 M200E-SMB
Sollevare
Levantar
Anheben
Fig./Abb. 2
Fig./Abb. 3
N200-505-00
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
60°C
-20°C
2
1
Rotate
Plug
Ruotare
Inserire
Girar
Conectar
Drehen
Einhaken
Clip / Agganciare
3
Acoplar / Einrasten
3
1
Lift
Push down
Premere
Precionar
hacia abajo
Runterdrücken
Rotate / Ruotare
2
Girar / Drehen
M710E-CZR
0905 22
DOP-IOD101
EN 54-17: 2005, EN 54-18: 2005
Notifier by Honeywell
Pittway Tecnologica S.r.l
Via Caboto 19/3
34147 Trieste, Italy
M710E-CZR
EN
This manual is intended as a quick reference installation guide. Please refer to the
control panel manufacturers installation manual for detailed system information.
The M700 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices.The M710E-CZR
M710E-CZR
is used to link a zone of conventional devices to an intelligent system controlled by
an addressable panel. The CZR has a resistor built in, making it especially suitable
for connection to a conventional zone that operates in a hazardous area requiring
intrinsically safe (IS) equipment.
The module must only be connected to Notifier control panels using analogue
addressable communication protocols for monitoring and control. The module is
M200E-SMB
compatible with System Sensor intrinsically safe sensors mounted in the B401 base,
for use with these barriers:
MTL model MTL4561, MTL5561 and Pepperl+Fuchs model KFD0-CS-EX1.51P,
KFD0-CS-EX2.51P.
NOTE: When an intrinsically safe system is used on the loop, a short on the sensor
side of the barrier will result in an alarm. Only a short on the module side of the safety
barrier will generate a fault signal.
A single tri-colour LED indicates the status of the module. In normal conditions, the
LED can be set by command from the control panel to blink green when the module
is polled. In the case of a fire alarm on the conventional zone, the LED is switched
on constant red by panel command. If a fault is detected on the conventional zone or
the zone supply voltage drops below 12 V, or a fault with the external power supply
is signalled, the LED will blink yellow if enabled on the control panel. When a short
circuit is detected on the loop to either side of the module, the LED is switched to show
a constant yellow light.
This module does not require maintenance.
SPECIFICATIONS
Intelligent Loop
Operating Voltage Range: see S00-7100
LED Cutoff Voltage: 16.5 V
Max. Standby Current (@24 V and 25
No Communication:
Max. Standby Current (@24 V and 25
EOL only (no detectors), Loop Powered Conventional Zone:
No Communication:
LED Current (Red):
LED Current (Yellow):
Isolator Features: see S00-7100
Conventional Zone
External Supply Voltage:
Maximum Standby Load Current: 2.8 mA for detectors at 18 V
Maximum Zone Load:
Maximum Conventional Line Resistance: 50 Ω
End of Line Resistor:
General
Humidity:
Ingress protection:
Maximum Wire Gauge:
INSTALLATION
M700 series modules can be mounted in several ways (See Figure 1):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132 mm (H) x 137 mm
(W) x 40 mm (D)
1:2 The DIN bracket on top allows mounting onto standard 35 mm x 7.5 mm "Top Hat"
DIN rail inside a control panel or other suitable enclosure. Install and remove as
shown in Figure 1:2
Wiring to all series M700 modules is via plug in type terminals capable of supporting
conductors up to 2.5 mm²
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches (see
Figure 3). A screwdriver should be used to rotate the wheels to select the desired
address, either from the front or the top of the module.
Note: The number of addresses available will be dependent on panel capability,
check the panel documentation for information on this.
Short Circuit Isolators
All M700 series modules are provided with short circuit monitoring and isolators on the
intelligent loop. If required the isolators may be wired out of the loop to facilitate the
use of the modules on high current loaded loops, for example if sounders are used.
To achieve this, the loop out positive should be wired to terminal 5 rather than terminal
2. See Figure 2 for details.
INSTALLATION INSTRUCTIONS - M710E-CZR
CONVENTIONAL ZONE INTERFACE MODULE
C) External Supply Conventional Zone:
o
C) Conventional Zone connected to resistive
o
1.3 mA
4.5 mA
12 to 28.5 V
18 to 28.5 V if conventional zone is loop powered
3.8 mA for detectors at 24 V
60 mA (limited internally)
3.9 kΩ, 5% (supplied)
5% to 95% relative humidity (non-condensing)
IP44 (Mounted in M200E-SMB)
2.5 mm²
CAUTION
120 µA
6.3 mA
I56-4421-000
loading

Resumen de contenidos para Honeywell NOTIFIER M710E-CZR

  • Página 1 34147 Trieste, Italy To achieve this, the loop out positive should be wired to terminal 5 rather than terminal 2. See Figure 2 for details. N200-505-00 Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ I56-4421-000...
  • Página 2 CAUTION LED corrente (rosso): 1,3 mA (sul comando del pannello) Electrostatic Sensitive Device LED corrente (giallo): 4,5 mA (in modalità isolamento) Observe precautions when handling and making connections Caratteristiche dell'Isolatore: vedere S00-7100 Zona convenzionale Tensione di alimentazione (esterno): 12-28,5 V (18-28,5 V se la zona convenzionale M710E-CZR Wiring è...
  • Página 3 Las conexiones de todos los módulos de la serie M700 se realizan mediante terminales extraíbles con capacidad para cables con sección de hasta 2,5 mm². N200-505-00 I56-4421-000 Honeywell Life Safety Iberia, S.L. C/ Pau Vila, 15-19, 08911 Badalona (Barcelona) Espana...
  • Página 4 INSTALLATIONSANLEITUNG FÜR M710E-CZR ACHTUNG INTERFACE-MODUL FÜR Elektrostatisch empfindliches Gerat Beachten Sie die Vorschriften STANDARDMELDERGRUPPEN fur den Umgang mit elektrostatisch empfindlichen Geraten Diese Kurzbedienungsanleitung ermöglicht einen schnellen Überblick zur Installation der Module. Für detaillierte Informationen lesen Sie bitte in der Installationsanleitung M710E-CZR Anschaltung der Brandmelderzentrale.