5. CONFIGURATION

Settings may only be changed by a qualified electrical engineer.
Read the instructions thoroughly before implementing changes.
During setting of the charger, the AC input must be removed.

5.1 Standard settings: ready for use

On delivery, the MultiPlus is set to standard factory values. In general, these settings are suitable for single-unit operation.
Warning:
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard MultiPlus factory settings
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on/ off
Battery charge curve
Charging current
Battery type
Automatic equalisation charging
Absorption voltage
Absorption time
Float voltage
Storage voltage
Repeated absorption time
Absorption repeat interval
Bulk protection
AC input current limit
UPS feature
Dynamic current limiter
WeakAC
BoostFactor
Auxiliary output
PowerAssist
Programmable relay

5.2 Explanation of settings

Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the software
configuration programs (see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50Hz; 60Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input frequency. The output
frequency is then equal to the input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this range with the AC input voltage. The output voltage is
then equal to the input voltage.
Adjustability:
Lower limit: 180 - 230V
Upper limit: 230 - 270V
Note: the standard lower limit setting of 180V is intended for stand alone operation only. In case of high power parallel or 3
phase systems, the lower input voltage limit stting must be increased to 210V or more.
Inverter voltage
Output voltage of the MultiPlus in battery operation.
Adjustability: 210 – 245V
50 Hz
45 - 65 Hz
180 - 265 VAC
230 VAC
stand-alone
off
on
on
four-stage adaptive with BatterySafe mode
75% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
off
14.4 / 28.8 / 57.6 V
up to 8 hours (depending on bulk time)
13.8 / 27.6 / 55.2 V
13.2 / 26.4 / 52.8V (not adjustable)
1 hour
7 days
on
50A (= adjustable current limit for PowerControl and PowerAssist functions)
on
off
off
2
25A
on
alarm function
11