DIP switch 3: Standard/corridor function:
oN/oFF = standard function
The lighting can also be switched on and offf using an external button.
oN = corridor function
The lighting can only be switched on using an external button.
DIP switch 4: Adjusting the sensitivity
The device is set to maximum sensitivity "S-max." in the factory settings.
If the switch is set to "S-min.", the level of sensitivity is reduced.
This setting is recommended if undesired switching occurs due to
interference sources, such as hot air streams.
7 • FUNCTIONS
Fully automatic mode
Light channel C1 will switch on automatically, depending on the preset
light value and detection of movement. This will remain on for as long
as movement is detected and as long as the ambient light value does
not exceed the preset light value. The HVAC channel is switched on when
movement is detected, regardless of the ambient light value. The time
settings for the respective channels will start if movement is no longer
detected. Each channel can also be manually switched on or off using
buttons S1 – S2. The device is preset to fully automatic mode.
Semi-automatic mode for light channel C1
Switched ON/OFF manually using the S1 button. They will remain on for
as long as movement is detected and as long as the ambient light value
does not exceed the preset light value.
Semi-automatic mode for HVAC channel
Switched ON/OFF using the S2 button. If movement is no longer detected,
the time setting for C2 will start and the lighting will switch off once the
set time has elapsed.
ECo semi-automatic mode for light channel C1
Light is switched on manually using the S1 button, no automatic activation.
If the ambient lighting level is darker than the preset light value,
the light channel is adjusted to this preset value. C1 will remain on
for as long as movement is detected and as long as the ambient light
value does not exceed the preset light value. However, if the ambient
lighting level is brighter than the preset light value, light channel C1 will
be set to the orientation light value and will switch off after 1 minute,
regardless of whether motion is detected or not. However, if light is
required, the desired brightness value must be set using the S1 button
before the set time elapses. In this case, light channel C1 will remain on for
as long as movement is detected, regardless of the ambient lighting level.
The HVAC channel is switched on when movement is detected, regardless
of the ambient light value. The time settings for the respective channels
will start if movement is no longer detected. Each channel can also be
manually switched on or off using buttons S1 – S2.
Corridor semi-automatic mode for light channel C1
Light is switched on manually using the S1 button, no automatic activation.
If the ambient lighting level is darker than the preset light value, light
channel C1 is adjusted to this preset value. This will remain on for as
long as movement is detected and as long as the ambient light value
does not exceed the respective light value. However, if the ambient
lighting level is brighter than the preset light value, the light channel is
adjusted to 100 % of the luminous efficiency. This will remain on for as