Accessories Supplied With The Unit - Technibel GR9FI140R7I Instrucciones De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
MONO SPLIT
DUAL SPLIT
GR9FI140
TRIAL SPLIT
QUADRI SPLIT
PENTA SPLIT
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln =
Maximum tubing length of a single indoor unit (n=1,2,3...)
L =
Keep Emix tubing as short as possible (MAX. 10/12m)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 " - 3/8" = 15g/m
For tubing 1/4 " - 1/2" = 20g/m
For tubing Emix (1/2") = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4, H5, H6)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
No additional charge of compressor oil is necessary.

ACCESSORIES SUPPLIED WITH THE UNIT

1. REDUCTION 1/2F - 3/8M + PIPE UNION 3/8 (2pcs)
2. REDUCTION 3/8F - 1/2M + PIPE UNION 1/2 (2pcs)
3. COVER (11pcs)
4. DRAIN TUBE
5. ADHESIVE DAMPER (4pcs)
6. TUBES 1/4 - 3/8 + 1/2 - 5/8 for HK (1set)
Tools required for installation (not supplied)
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8. Core bits ø 5
AT SHIPMENT
L Tot. (m)
L n (m)
40
-
40
30
40
30
40
30
40
30
19.Hammer
10.Drill
11. Tube cutter
12.Tube flaring tool
13.Torque wrench
14.Adjustable wrench
15.Reamer (for
reburring)
16.Hex. key
ADDITIONAL REFRIGERANT
L Tot. (m)
L n (m)
50
100
100
100
100
5
REGULATION (EU) No. 517/2014 - F-GAS
The unit contains R410A, a fluorinated greenhouse gas with
a global warming potential (GWP) of 2087.50. Do not
release R410A into the atmosphere.
R410A: 4.40 kg / 9.19 Tonn.CO2
7
MINIMUM LENGTH
L (m)
-
5
30
5
30
5
30
5
30
5
1
2
6
EG
3
4
Tabla de contenido
loading

Tabla de contenido