GB
Specification
All manuals and user guides at all-guides.com
Construction
Wetside material
316/316L Stainless steel (1.4401/1.4404) dual-certified,
Alloy C (UNS N10002) and Alloy C-276 (UNS N10276), or
ECTFE co-polymer coating
Gasket
Non-asbestos BS7531 Grade X carbon
(1" BSPP (G1) only)
fibre with rubber binder
Housing Code
A
Housing
Nylon PA66
material
30%GF
LED Window
PMMA
Conduit Entry
M20
Weather
IP66/67 to
proofing
EN60529
Operating conditions
Wetside temp.
-40C to +150C
Ambient temp.
-40C to + 80C
(derated to 50C at 150C wetside)
Wetside pressure
-0.25 bar g to +100 bar g at 50C
(30 bar for hygienic fittings)
Liquid sg
0.6 to 2.0
Liquid viscosity
0.2 to 10,000 cps
Switching point (H
0)
13 mm from tip (vertical)
2
13 mm from edge (horizontal)
1 mm nom.
Hysteresis (water)
Switching delay
0.3, 1, 3, 10, 30 sec dry to wet / wet to dry.
Maximum altitude
2000 metres
Maximum humidity
EN 60068-2-30:2005 (90% RH)
Electrical
Switching mode
User selectable (Dry = on or Wet = on)
Protection
Reverse polarity protected. Missing load / short-circuit protection.
Terminal connection
(wire diameter)
Max. 2.5 mm
Cable gland
Supplied with PA66 only – cable dia. 5 mm to 8 mm.
Earthing
SQUING 2 must always be earthed either through
terminals or using external earth connection provided.
Safety EMC
E.M.C. Directive
EN61326 Emissions to Class B.
Immunity to industrial location requirements.
L.V. Directive
EN61010-1
Pollution degree 2, Category II (264V max)
Pollution degree 2, Category III (150V max)
Page 37
D
X
Y
Al alloy ASTM
B85 A360.0
-
½"
M20
¾" NPT
NPT
IP66/67 to
EN60529,
NEMA 4X
2
(Note national regulations)
S
T
316C12 SST
-
M20
¾" NPT
IP66/67 to
EN60529,
NEMA 4X
IP2025
Tabla de contenido