Code
J45
Signal assignment to:
(for relay output card)
J46
J47
J48
Cumulative run time of motor
J49
J50
J51
J52
J53
Maximum cumulative number of relay
J54
ON times
J55
Y codes: Link functions
Code
Y01
RS485 communication
(standard)
Y02
Y03
Y04
Y05
Y06
Y07
Y08
Y09
Y10
Y11
RS485 communication
Y12
(option)
Y13
Y14
Y15
Y16
Y17
Y18
Y19
Y20
Name
[Y1 A/B/C]
Selecting function code data assigns the corresponding function to
terminals [Y1A/B/C], [Y2A/B/C] and [Y3A/B/C]
[Y2 A/B/C]
[Y3 A/B/C]
100: Depends on the setting of E20 to E22
60 (1060 ): Sequenced start motor 1, inverter-driven
61 (1061): Sequenced start motor 1, commercial power -
driven
62 (1062): Sequenced start motor 2, inverter-driven
63 (1063): Sequenced start motor 2, commercial power -
driven
64 (1064): Sequenced start motor 3, inverter-driven
65 (1065): Sequenced start motor 3, commercial power -
driven
67 (1067): Sequenced start motor 4, commercial power -
driven
68 (1068): Periodic switching early warning
69 (1069): Pump control limit signal
Motor 0
Indication of cumulative run time of motor for replacement
Motor 1
Motor 2
Motor 3
Motor 4
Y1 A/B/C to Y3 A/B/C
1.000 means 1.000 times
[Y1], [Y2], [Y3]
For relay output card
[Y5A/C], [30A/B/C]
For built-in mechanical contacts
Name
Station address
1 to 255
Communications error processing
0: Immediately trip with alarm Er8
1: Trip with alarm Er8 after running for the period specified by timer y03
2: Retry during the period specified by timer y03. If retry fails, trip and
alarm Er8. If it succeeds, continue to run
3: Continue to run
Error processing timer
0.0 to 60.0 seconds
Transmission speed
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Data length
0: 8 bits
1: 7 bits
Parity check
0: None
1: Even parity
2: Odd parity
Stop bits
0: 2 bits
1: 1 bit
No-response error detection time
0 (No detection)
1 to 60 seconds
Response latency time
0.00 to 1.00 seconds
Protocol selection
0: Modbus RTU protocol
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
3: Metasys-N2
Station address
1 to 255
Communications error processing
0: Immediately trip with alarm ErP
1: Trip with alarm ErP after running for the period specified by timer y03
2: Retry during the period specified by timer y03. If retry fails, trip and
alarm ErP. If it succeeds, continue to run
3: Continue to run
Error processing timer
0.0 to 60.0 seconds
Transmission speed
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
Data length
0: 8 bits
1: 7 bits
Parity check
0: None
1: Even parity
2: Odd parity
Stop bits
0: 2 bits
1: 1 bit
No-response error detection time
0 (No detection)
1 to 60 seconds
Response latency time
0.00 to 1.00 seconds
Protocol selection
0: Modbus RTU protocol
2: Fuji general-purpose inverter protocol
3: Metasys-N2
Chapter 6: Function codes and application example
Data setting range
(M1_I)
(M1_L)
(M2_I)
(M2_L)
(M3_I)
(M3_L)
(M4_L)
(MCHG)
(MLIM)
Data setting range
Default setting
100
100
100
---
---
---
---
---
---
---
---
Default setting
1
0
2.0 seconds
3
0
0
0
0
0.01 seconds
1
1
0
2.0 seconds
3
0
0
0
0
0.01 seconds
0