P codes: Motor parameters
Code
P01
Motor
P02
P03
P04
P06
P07
P08
P99
H codes: High performance functions
Code
H03
Data initialization
H04
Auto-resetting
H05
H06
Cooling fan ON/OFF control
H07
Acceleration/Deceleration pattern
H09
Select starting characteristics
(Auto search for idling motor's speed)
H11
Deceleration mode
H12
Instantaneous overcurrent limiting
H13
Restart mode after
momentary power failure
H14
H15
H16
H17
Select starting characteristics (Frequency for idling motor's
speed)
H26
PTC thermistor input
H27
H30
Communication link function (Mode selection)
Name
No. of poles
2 to 22
Rated capacity
0.01 to 1000 kW (If P99 is 0, 3 or 4)
0.01 to 1000 HP (If P99 is 1)
Rated current
0.00 to 2000 A
Auto-tuning
0: Disable
1: Enable (Tune %R1 and %X while the motor is stopped)
2: Enable (Tune %R1 and %X while the motor is stopped and no-load
current while running)
No-load current
0.00 to 2000 A
%R1
0.00 to 50.00 %
% X
0.00 to 50.00 %
Motor selection
0: Characteristics of motor 0
(Fuji standard motors, 8-series)
1: Characteristics of motor 1 (HP -rated motors)
3: Characteristics of motor 3 (Fuji standard motors, 6-series)
4: Other motors
The shaded function codes are applicable to the quick setup menu
Name
0: Disable initialization
1: Initialize all function code data to the factory defaults
2: Initialize motor parameters
Times
0: Disable
1 to 10 times
Reset interval
0.5 to 20.0 seconds
0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
0: Linear
1: S-curve (Weak)
2: S-curve (Strong)
3: Curvilinear
0: Disable
3: Enable (Follow RUN command, either forward or reverse)
4: Enable (Follow RUN command, both forward and reverse)
5: Enable (Follow RUN command, inversely both forward and
reverse)
0: Normal deceleration
1: Coast-to -stop
0: Disable
1: Enable
Restart time
0.1 to 10.0 seconds
Frequency fall rate
0.00: Set deceleration time
0.01 to 100.0 Hz/s
999: Follow the current limit command
Continuous running level
200V series: 200 to 300VDC
400V series: 400 to 600VDC
Allowable momentary power
0.0 to 30.0 seconds
failure time
999: The longest time automatically determined by the inverter
0.0 to 120.0 Hz
999: Harmonize at the maximum frequency
Mode selection
0: Disable
1: Enable (Upon detection of PTC, the inverter immediately trips
and stops with OH4 displayed)
2: Enable (Upon detection of PTC, the inverter continues running
while outputting alarm signal (THM))
Level
0.00 to 5.00 V DC
Frequency command
0: F01/C30
1: RS485 link
2: F01/C30
3: RS485 link
4: RS485 link (option)
5: RS485 link (option)
6: F01/C30
7: RS485 link
8: RS485 link (option)
Chapter 6: Function codes and application example
Data setting range
Data setting range
RUN command
F02
F02
RS485 link
RS485 link
F02
RS485 link
RS485 link (option)
RS485 link (option)
RS485 link (option)
Default setting
4
Rated capacity of the
motor
Rated current of Fuji
standard motor
0
Rated value of Fuji
standard motor
0
Default setting
0
0 times
5.0 seconds
0
0
0
0
1
Depending on the inverter
capacity
999
235 V DC
470 V DC
999
999
0
1.60 V DC
0
17