Fuji Electric FRENIC-Eco FRN-F1 Serie Guía Rápida página 22

Variador de frecuencia para control de bombas y ventilación
Ocultar thumbs Ver también para FRENIC-Eco FRN-F1 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

J codes: Application functions
Code
J01
PID control
Mode selection
J02
Remote process command
J03
P (gain)
J04
I (integration time)
J05
D (differential time)
J06
Feedback filter
J10
Anti reset windup
J11
Select alarm output
J12
Upper limit alarm (AH)
J13
Lower limit alarm (AL)
J15
Stop frequency for slow flowrate
J16
Slow flowrate level stop latency
J17
Starting frequency
J18
Upper limit of PID process output
J19
Lower limit of PID process output
J21
Dew condensation prevention (Duty)
J22
Commercial power switching sequence
J25
Pump control
J26
Motor 1 mode
J27
Motor 2 mode
J28
Motor 3 mode
J29
Motor 4 mode
J30
Motor switching order
J31
Motor stop mode
J32
Periodic switching time for motor drive
J33
Periodic switching signaling period
J34
Sequenced start of commerc ial power-
driven motor
J35
J36
Sequenced stop of commercial power -
driven motor
J37
J38
Contactor delay time
J39
Switching time for motor sequenced start (Deceleration time)
J40
Switching time for motor sequenced stop (Acceleration time)
J41
Motor sequenced start/sequenced stop switching level
J42
Switching motor sequenced start/sequenced stop (Dead band)
J43
PID control startup frequency
Name
0: Disable
1: Enable (normal operation)
2: Enable (inverse operation)
0: Enable arrow keys on keypad
1: PID process command 1
3: Enable terminal command UP/DOWN control
4: Command via communications link
0.000 to 30.000 times
0.0 to 3600.0 seconds
0.00 to 600.0 seconds
0.0 to 900.0 seconds
0 to 200 %
(Refer to FRENIC -Eco user's manual)
0 to 100 %
0 to 100 %
0: Disable
1 to 120 Hz
1 to 60 seconds
0: Disable
1 to 120 Hz
1 to 120 Hz
999: Depends on setting of F15
1 to 120 Hz
999: Depends on setting of F16
1 to 50 %
0: Keep inverter operation (Stop due to alarm)
1: Automatically switch to commercial-power operation
Mode selection
0: Disable
1: Enable (Fixed, inverter driven)
2: Enable (Floating, inverter driven)
0: Disable (Always OFF)
1: Enable
2: Force to run by commercial power
0: Fixed
1: Automatically (Constant run time)
0: Stop all motors (inverter-driven and commercial power -driven)
1: Stop inverter-driven motor only (excl. alarm state)
2: Stop inverter-driven motor only (incl. alarm state)
0.0: Disable switching
0.1 to 720.0: Switching time range
999: Fix to 3 minutes
0.1 to 600.0 seconds
Frequency
0 to 120 Hz
999: Depends on setting of J18
(This code is used to judge whether or not to stop a commercial power -
driven motor by checking the output frequency of the inverter-driven
motor)
Duration
0.00 to 3600 seconds
Frequency
0 to 120 Hz
999: Depends on setting of J19
(This code is used to judge whether or not to stop a commercial power -
driven motor by checking the output frequency of the inverter-driven
motor)
Duration
0.00 to 3600 seconds
0.01 to 2.00 seconds
0.00: Depends on the setting of F08, 0.01 to 3600
0.01 to 3600 seconds
0.00: Depends on the setting of F07, 0.01 to 3600
0.01 to 3600 seconds
0 to 100 %
0.0: Disable
0.1 to 50.0 %
0: Disable
1 to 120Hz
999: Depends on the setting of J36
Chapter 6: Function codes and application example
Data setting range
Default setting
0
0
0.100 times
0.0 seconds
0.00 seconds
0.5 seconds
200 %
0
100 %
0 %
0
30 seconds
0
999
999
1 %
0
0
0
0
0
0
0
0
0.0 seconds
0.1 seconds
999
0.00 seconds
999
0.00 seconds
0.00 seconds
0.00 seconds
0.00 seconds
0 %
0.0 %
999
19
Tabla de contenido