Pool Pump Suction Entrapment Prevention Guidelines - Jandy JCP Serie Manual De Instrucciones

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Page 5
ENGLISH
|
Jandy
JCP Series High Performance Commercial Pumps
Installation & Operation Manual
®
1.2

Pool Pump Suction Entrapment Prevention Guidelines

CAUTION
The performance of Jandy pumps is based upon clear, cold, fresh water with suction conditions as shown on the
performance curve. If used to pump other liquids, pump performance may differ from rated performance based
on the different specific gravity, temperature, viscosity, etc. of the liquid being pumped. A standard pump may
not be safe for pumping all types of liquids, such as toxic, volatile or chemical liquids, or liquids under extreme
temperatures or pressures. Please consult Jandy catalogs as well as local codes and general references to
determine the appropriate pumps for your particular application. Since it is impossible for us to anticipate every
application of a Jandy pump, if you plan to use the pump for a non-water application, consult Jandy beforehand to
determine whether such application may be proper or safe under the circumstances. Failure to do so could result
in property damage or personal injury.
WARNING
Pump suction is hazardous and can trap and drown or disembowel bathers. Do not use or
operate swimming pools, spas, or hot tubs if a suction outlet cover is missing, broken, or loose.
The following guidelines provide information for pump installation that minimizes risk of injury to users of
pools, spas, and hot tubs:
Entrapment Protection - The pump suction system must provide protection against the hazards of
suction entrapment.
Suction Outlet Covers - All suction outlets must have correctly installed, screw-fastened covers in
place. All suction outlet (drain) covers must be properly maintained. They must be replaced if cracked,
broken, or missing. Drain covers must be listed/certified to the latest published edition of ANSI
/ASME
®
®
A112.19.8 or its successor standard, ANSI/APSP-16. The pool must be shut down and bathers must be
restricted from entering the pool until any cracked, broken, or missing drain covers are replaced.
Number of Suction Outlets Per Pump - Provide at least two (2) hydraulically-balanced suction outlets,
with covers, as suction outlets for each circulating pump suction line. The centers of the suction outlets
(suction outlets) on any one (1) suction line must be at least three (3) feet apart, center to center. See
Figure 1.
The system must be built to include at least two (2) suction outlets (drains) connected to the pump
whenever the pump is running. However, if two (2) suction outlets run into a single suction line, the
single suction line may be equipped with a valve that will shut off both suction outlets from the pump.
The system shall be constructed such that it shall not allow for separate or independent shutoff or
isolation of each drain. See Figure 1.
Additional pumps can be connected to a single suction line as long as the requirements above are met.
Water Velocity - The maximum water velocity through the suction outlet assembly and its cover for any
suction outlet must not exceed the suction outlet assembly and its cover's maximum design flow rate.
The suction outlet (drain) assembly and its cover must comply with the latest version of ANSI
/ASME
®
®
A112.19.8, the standard for Suction Fittings For Use in Swimming Pools, Wading Pools, Spas,and Hot
Tubs, or its successor standard, ANSI/ASME APSP-16.
Testing and Certification - Suction outlet covers must have been tested by a nationally recognized
testing laboratory and found to comply with the latest published edition of ANSI/ASME A112.19.8 or
its successor standard, ANSI/APSP-16, the standard for Suction Fittings For Use in Swimming pools,
Wading Pools, Spas, and Hot Tubs.
Fittings - Fittings restrict flow; for best efficiency use fewest possible fittings (but at least two (2) suction
outlets).
Avoid fittings that could cause an air trap.
Pool cleaner suction fittings must conform to applicable International Association of Plumbing and
Mechanical Officials (IAPMO) standards.