2.5.3 Preheat freshwater station (C)
Preheating the DHW with the freshwater station
•
With the preheat freshwater station the water is preheated
according to the instantaneous water heating principle
when water is drawn off. A heat generator in a DHW cylinder
then brings the DHW up to the set temperature.
2.5.4 Therm.dis./daily heat-up (D)
Thermal disinfection to avoid legionella ( Drinking Water
Ordinance [Germany])
•
Each day the entire DHW volume and the preheat
freshwater station are heated until the set daily heat-up
temperature is reached.
This function can only be used together with the preheat
freshwater station (C).
2.5.5 Cascade (E)
Cascading of the freshwater stations for higher draw-off flow
rates
•
Additional freshwater stations are connected when larger
volumes are drawn off.
•
This function controls several connected freshwater
stations.
2.6
Scope of delivery
Fig. 3 at end of document:
[1] Module
[2] Storage cylinder temperature sensor
[3] Collector temperature sensor
[4] Bag with strain relief
[5] Installer Guide
MS 100 – 6721830547 (2020/12)
0 010 013 297-001
0 010 013 298-001
0 010 013 299-001
2.7
Declaration of conformity
The design and operating characteristics of this product
comply with the European and national directives.
The CE marking declares that the product complies
with all the applicable EU legislation, which is
stipulated by attaching this marking.
The complete text of the Declaration of Conformity is available
on the Internet: www.bosch-thermotechnology.com.
2.8
Tech data
Tech data
Dimensions (W × H × D)
Maximum conductor cross-
section
•
230 V terminal
•
Extra-low voltage terminal •
Rated voltages
•
BUS
•
Module mains voltage
•
Remote control
•
Pumps and mixers
Fuse
BUS interface
Power consumption –
Standby
Maximum power output
•
per connection(PS1)
•
per connection (VS1,
PS2, PS3)
Measuring range of cylinder
temperature sensor
•
Lower fault limit
•
Display area
•
Upper fault limit
Measuring range, collector
temperature sensor
•
Lower fault limit
•
Display area
•
Upper fault limit
About the product
151 × 184 × 61 mm
(for more dimensions
Fig. 4 at end of document)
2
•
2.5 mm
2
1.5 mm
•
15 V DC (reverse polarity
protected)
•
230 V AC, 50 Hz
•
15 V DC (reverse polarity
protected)
•
230 V AC, 50 Hz
230 V, 5 AT
EMS 2/EMS plus
< 1 W
400 W (high-efficiency
pumps permissible; <30 A for
10 ms)
•
≤ -10 °C
•
0 ... 100 °C
•
> 125 °C
•
≤ -35 °C
•
-30 ... 200 °C
•
> 230 °C