Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
Indoor
power cord
Remote
controller
cord
24k/34k Btu/h (1Ø)
• Cooling & Heating type
Terminals on the indoor unit
Terminals on the outdoor unit
POWER
INPUT
The power cord connected to the outdoor unit should be
complied with the following specifications (Rubber
insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent.
W
ARNING:
Make sure that the screws of the terminal are free from looseness.
All manuals and user guides at all-guides.com
Control box cover
Control box cover screw
1(L)
2(N)
1(L) 2(N)
1(L)
2(N)
CAUTION
Capacity
1 Phase
2
24k Btu/h
2.1mm
2
34k Btu/h
3.3mm
3
4
5
3
4
5
The connecting cable connected to the indoor and outdoor
unit should be complied with the following specifications
(Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL
CROSS-SECTIONAL
AREA 2.1mm
Wiring Connection
[Air inlet side view]
2
(24k/34k)
Installation Manual 11