BLUEHELIX MAXIMA
Transparent Parameters "P" menu
By selecting a parameter on the screen, the possible values will be shown. If the values shown do not match
A
those indicated in the corresponding "Range" column, check that the parameter B01 is correctly set to RRT.
Code Description
P30 Heating ramp
Virtual set point min. tempe-
P31
rature
P32 Heating standby time
P33 Heating Post-Circulation
P34 Pump operation
Modulating pump min.
P35
speed
Modulating pump start
P36
speed
Modulating pump max.
P37
speed
Pump deactivation tempera-
P38
ture during Post-Circulation
Pump activation hysteresis
temperature during Post-
P39
Circulation
P40 Heating user max. setpoint
P41 Max. output in heating
P42 Burner shutdown in DHW
Comfort mode activation
P43
temperature
Comfort mode deactivation
P44
hysteresis
P45 DHW standby time
P46 DHW user max. setpoint
P47 DHW pump Post-Circulation 0 ÷ 255 seconds
P48 Max. output in DHW
P49 Not implemented
P50 Not implemented
P51 Solar off temperature
P52 Solar on temperature
P53 Solar standby time
Heating deltaT adjustment
P54
temperature
Primary exchanger protec-
P55
tion temperature
P56 System min. pressure value 0 ÷ 8bar/10
System nominal pressure
P57
value
Exchanger protection inter-
P58
vention (b01=3)
Heating hysteresis after
P59
ignition
Timer for heating hysteresis
P60
after ignition
Pump deactivation with
P61
OpenTherm
EN
Range
1 ÷ 20°C/minute
0= Deactivated
1 ÷ 80°C
0 ÷ 10 minutes
0 ÷ 255 minutes
Fixed flow rate on call
Fixed continuous flow rate
Adaptive flow rate on call
Adaptive continuous flow rate
30 ÷ 100%
90 ÷ 100%
90 ÷ 100%
0 ÷ 100°C
0 ÷ 100°C
20 ÷ 90°C
0 ÷ 100%
Fixed
Linked to setpoint
Solar
0 ÷ 80°C
0 ÷ 20°C
30 ÷ 255 seconds
40 ÷ 70°C
0 ÷ 100%
--
--
0 ÷ 100°C
0 ÷ 100°C
0 ÷ 255 seconds
0 ÷ 60°C
0 ÷ 150°C
5 ÷ 20bar/10
0 = No F43
1 ÷ 15 = 1 ÷ 15°C/second
6 ÷ 30°C
60 ÷ 180 seconds
0 ÷ 1
cod. 3541U630 - Rev. 00 - 07/2020
Default
4°C/minute
0
4
15
Adaptive flow rate on call
30%
90%
100%
55°C
25°C
80°C
80%
Fixed
40°C
20°C
120
55°C
30
BLUEHELIX MAXIMA 24C = 86%
BLUEHELIX MAXIMA 28C = 100%
BLUEHELIX MAXIMA 34C = 100%
--
--
10°C
10°C
10
18°C
43°C
4 bar/10
7 bar/10
10°C/second
10°C
60
0
209