Wiring: 0–10 VDC automation
WARNING: To reduce the risk of electric shock, wiring should be performed by a qualified electrician! Incorrect assembly
can cause electric shock or damage the motor and the controller! Hazard of electrical shock!
CAUTION: Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable
codes and standards.
0–1 VDC = Fan off
1–10 VDC = Fan run and speed reference
Fan speed % per
VDC applied
VDC In % Speed
0–1
Fan off
1–10
15–100%
100
90
80
70
60
50
40
30
20
10
0
0 1 2 3 4 5 6 7 8 9 10
VDC In
Attach the snap-on ferrite core to the controller input cable within 1 ft
STOP
(305 mm) of the top of the extension tube to minimize electrical noise.
All manuals and user guides at all-guides.com
ESSENCE
Wiring the Fan (cont.)
Controller Input Cable
1
White
+0–10 VDC Speed Ref.
2
Brown
Not Used
3
Orange Status LED (+)
4
Yellow
Run Enable
Closed: Enable, Open: Disable*
5
Blue
6
Green
Status LED (-)
7
Red
+10 VDC Supply
8
Black
DC Common
WWW.BIGASSFANS.COM
©2013 DELTA T CORP.
®
BLUE & YELLOW
Run enable
Controller
Closed: enable
Open: disable*
Input Cable
Ferrite core
ALL RIGHTS RESERVED
*Note: If this circuit is open, the fan will shut
down and issue a Run Enable Jumper Open
error. The jumper must stay closed for the fan
to run. A zero speed reference (under 1 V) will
bring the fan to a stop. To restart the fan, close
the circuit and reset power to the fan.
1–10 V Analog
Speed Reference