4. ELECTRICAL FEATURES

Switch Socket Type
Rated Voltage
AC3
Category
AC22A
AC23A
4.1 CROSS SECTIONAL AREAS CONDUCTORS & TORQUE
Switch Socket Type
16A
32A
63A
125A
4.1.1 Earth Terminals
Type
16/32A
63A
125A

4.2 AUXILIARY CONTACTS

In the sockets ADVANCE-GRP[GD] type 16A, 32A, and 63A can be install as optional 2 auxiliary contacts maximum, on model type
125A is not possible to install auxiliary contacts.
They are optional accessories with ATEX / IECEx / EAC Ex separate certificates. Installation and maintenance shall be done as
prescribed by manufacturer documents. Creepage and clearance distances shall comply with IEC EN 60079-7 / ГОСТ Р МЭК
60079-7-2012 at Table 1, current and maximum dissipated power shall not exceed the maximum value allowed.
4.3 HOW TO INSTALL AUXILIARY CONTACT
ADVANCE-GRP[GD] 16/32A
MP39683
16/32A
400V
500V
690V
-
25A
-
-
-
32A
-
32A
-
SWITCH TERMINALS CONTACTS - TORQUE
Cross Sectional Areas Conductors
Minimum
4 mm²
6 mm²
16 mm²
50 mm²
EARTH TERMINALS CONTACTS - TORQUE
Cross Sectional Areas Conductors
10/16 mm²
Weidmuller Ex e terminal - type WPE35 35mm²
50/70mm² - CZ0513-180A - Switch-Earth Terminal
Insertion aux. contact "B"
B
A
Insertion aux. contact "A"
63A
400V
500V
-
50A
-
-
-
-
Maximum
10 mm²
10 mm²
25 mm²
70 mm²
ADVANCE-GRP[GD] 63A
17
CZ0513-180A
690V
690V
-
125A
63A
125A
63A
125A
Tightening Torque -
(Nm)
0.8
2.5
3.5
Tightening Torque - (Nm)
1.2
3.5
Insertion aux. contact "B"
B
A
Insertion aux. contact "A"
ZP90904-5