T5000-E
Instructions
• On/off: press
to turn on, press again to turn off, close the fan and valve.
• Setting temperature: Press either
• Mode selection: press
• Fan speed selection: press
Under "AUTO" mode, the fan-speed will be changed automatically. Auto LOW-speed when the difference between room
temperature and set-point exceed 1 °C, Auto MED-speed when exceed 2 °C, Auto HI-speed when exceed 3 °C.
• Valve Control: under cool (heat) mode, the valve will be open while the difference between room temperature and setpoint
exceed 1 °C; while the room temperature reaches setpoint, the valve is closed with the fan still running.
Time-On and Time-Off Operation
• Hold down the
button for 3 seconds will enter the Timer On-Off setting. When the
M
keys to set the duration of the time delay for automatic switch ON.
Press
button again,
M
OFF. Set time duration to
After one cycle for Time-on and Time-off the setting will be automatically canceled.

Lock function

• Lock function: The thermostat will be locked automatically after 0 seconds under the lock function. Hold down the fan key 5
seconds to unlock.
Unoccupied energy-saving mode (T5200-TB-9JS0)
• Unoccupied energy-saving mode (by entrance card): While entrance card is pulled out, the temperature automatically set to
26 °C, fan is on LO-speed if the thermostat is in cool mode; the temperature set to 18 °C, fan is on LO-speed if in heat mode.
Low Temperature protection setting
• On power Off status and when room temperature is lower than 5 °C, heat function will be automatically switched on,
the fan is set to HI-speed and the valve (heat valve for T5200-TF-9JS0) is opened. When the room temperature reaches 7 °C, the
setting will be automatically canceled.
• On power Off status, press
cancelling low temperature protection,

Temperature setting

If customers hope the displayed temperature higher or lower than the real temperature, operate as follows:
• On power off status, press both
the temperature, auto-confirmed after 6 seconds.
Alarm
• When the sensor is in fault, thermostat will close the fan and valve, display
: Sensor short cut alarm
E1
: Sensor circuit breaker alarm
E2
Display
, temperature > 55 °C; display
HI
Functional Code Setting Table (only when Thermostat is OFF)
• Enable the setting table: hold down the
code, use
and
buttons to adjust the value.
T5200-
T5200-
Code
TB-9JS0
TF-9JS0
01
02
03
04
05
06
---
06
---
07
---
08
---
P/N 24-85784-119 Rev. - Issue Date 11 2012
or
buttons to increase or decrease the setpoint by 0.5 °C.
to change the working mode,
M
to choose the speed
,
and
appear, press
hh
--
, to cancel the setting.
and keep 5 seconds, display
M
means the protection function is on. Factory setting is
ON
and
, keep 5 seconds, display
, temperature < 0 °C
and
Parameter Name
°F / °C
Upper limit of set temp
Lower limit of set temp
Keypad lockout
Screen Display
Auto or Manual Mode Switch
Key Card Status
Cooling Temp when key card is pulled out 26.0 °C Setting Range 22 ~ 32 °C
Heating Temp when key card is pulled out 18.0 °C Setting Range 10 ~ 21 °C
cooling,
heating,
(hi),
(med),
(low),
and
keys to set the duration of the time delay for automatic switch
or
, press
ON
(no working mode display), press
XX °C
,
for 5 seconds, 01 and code appeare, after which press
Defaulf Function
C
35.0 °C Setting Range 2 ~ 49.5 °C
5.0 °C
00
00
00
01
English
ventilating (no heat mode for T5200-TC-9JS0)
(auto).
,
and
appear, press
hh
ON
,
to adjust the parameter.
.
and
.
E1
E2
F: Fahrenheit Degree (°F)
C: Celsius Degree (°C)
Setting Range 0 ~ 47.5 °C
00: No lock
01: Lock all keys
02: Lock ON/OFF key
03: Lock the keys except ON/OFF key
00: Display room temp
01: Display set temp
00: Manual Mode
01: Auto Mode
00: S1, S2 Short Connection indicates key card is
inserted;
Disconnection indicates key card is pulled out
01: S1, S2 Disconnection indicates key card is
inserted;
Short Connection indicates key card is pulled out
and
appears,
means
or
adjust
button to select
M