6. Operation

6.1 A.C. IU Parameters (SW8: Setting 0 – All in OFF)
Code
Description
AI1
Inlet temperature
AI2
Outlet temperature
AI3
Not available
AI4
Not available
AI5
Not available
AI6
Not available
AI7
Not available
AI8
Not available
DI1
Fan unit ON/OFF
DI2
Fan HIGH speed
DI3
Fan MEDIUM speed
DI4
Fan LOW speed
DI5
Alarm code
DI6
ON/OFF status
DI7
Not available
DI8
Not available
O1
Fan unit ON/OFF
O2
Fan HIGH speed
O3
Fan MEDIUM speed
O4
Fan LOW speed
O5
Heat/Cool mode
O6
Central/Local mode
O7
Alarm signal
O8
Not available
1) If some of DI2~4 are activated at the same time, the lower speed is selected.
2) If some of those terminals are not available or accesible from fan unit, then those functions are not available.
Some functions activated by local Remore Controller (ON/OFF and FAN SPEED).
All these parameters can be used for other purposes different from those indicated in the previous table. In that case, it is
recommended to keep in local mode, just to avoid the undesired performance of that parameter in case of central control.
Those functions in central mode can be operated from CSNET WEB as normal Hitachi Indoor Unit
PMML0169A rev0 - 12/2007
Connection
Temperature sensor (optional)
Temperature sensor (optional)
From local remote controller
From local remote controller
From local remote controller
From local remote controller
From local remote controller
From fan unit (feedback signal)
Unit fan: ON/OFF terminals
Unit fan: HIGH speed terminals
Unit fan: MEDIUM speed terminals
Unit fan: LOW speed terminals
Unit fan: Operation mode terminals
Local Remote Controller: Lamp
To Local Remote Controller
HARC I/O - xxxxxxxxxxxxxxxx
HARC I/O - Installation Manual
Remarks
Local
PT1000
Applicable
PT1000
Applicable
OFF: Open
Applicable
ON: Closed
Selector switch:
Applicable
Selected switch is
closed circuit (1)
Alarm OFF: Open
Applicable
Alarm ON: Closed
OFF: Open
Applicable
ON: Closed
OFF: Open
Applicable
ON: Closed
OFF: Disabled
Applicable
ON: Activated
(2)
COOL: Open
Applicable
HEAT: Closed
(2)
OFF: Local
Applicable
ON: Central
OFF: Alarm OFF
Applicable
ON: Alarm ON
11
11 11
Central
Monitoring
Monitoring
Monitoring
Monitoring
Monitoring
Monitoring
Control
Control
Control
Control
Control