Function settings (continued)
Operation monitor output synchronized
No.57
with exhaust fan or supply fan
Set operation monitor output from TM3 90 synchronized with
supply of exhaust fan.
Also supply fan delay operation, ex. for after-heater, can be set.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
2-8 OFF
5-2 OFF
(Factory setting)
2-8 OFF
SW2-8
57
5-2 ON
SW5-2
2-8 ON
(Either
5-2 ON or
OFF)
To use SW2-8 as the after-heater, observe the cautions listed in
the page 11.
By-pass monitor output or Pre-heater
No.58
output setting
Set By-pass monitor or Pre-heater output from TM3 70
synchronized with supply of exhaust fan.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
(Factory setting)
SW5-6
58
ON
- For heater selection, observe the cautions listed in
11.
- When set to auto ventilation mode while using the Pre-heater
function, the outdoor temperature may be detected as higher and
the mode may change to By-pass mode, even in winter.
- During pre-heater is ON, Lossnay does not go to Fan speed 1.
Even remote controller displays Fan speed 1, Lossnay is operated
at Fan speed 2.
Eng-20
Setting
Operation monitor
check
output from TM390
0
DIP-SW priority
(Factory setting)
1
EA fan monitor output
SA fan monitor output
* When supply fan stops
2
during cold outdoor temp.
or defrosting, output stops.
Operation monitor output
corresponds with supply
fan with following.
Starts the output 10 seconds
3
after supply fan operates.
Fan continues to operate
supply fan for 3 min after
stopping the output.
Setting
Output setting from
check
TM370
0
DIP-SW priority
(Factory setting)
By-pass ventilation
operation monitor
1
output. Corresponds to
operation mode output
of By-pass damper.
Pre-heater output.
Corresponds to operation
output supply fan with
following. Start the output
10 seconds after supply
fan starts. Fan continues
to operate for 3 min after
stopping the output. Lossnay
starts output when outdoor
temp. 0˚C or less, and stops
output when detecting temp.
2
becomes 15˚C. Lossnay stop
the output every 1 hour. Error
code is shown on the remote
controller and stop the output
in case of following.
1) TH1 detects higher than
15 ˚C within 15 minutes after
the output starts.
2) TH1 detects -10 ˚C or
lower, 60 minutes after the
output starts.
4
on the page
Pre-heater output setting 1)
No.59
ON temperature
Set the outdoor temperature for Pre-heater output ON.
When detecting temp. becomes the setting or less, Pre-heater output
from TM370 starts.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
Setting
check
SW No.
Setting
-
-
-
-
N/A
-
-
-
-
Pre-heater output setting 2)
No.60
OFF interval
Set the Pre-heater output interval. Output stops according to the set
hours.
4
on
DIP-SW
Setting
check
SW No.
Setting
-
-
N/A
-
-
-
No.61
Fan speed for air volume "High" input
Set the fan speed setting when receiving "High" signal from remote
controllers(e.g. remote controller of City Multi and Mr. Slim, Lossnay
simple remote controller) which have High/Low or High/Middle/Low
air volume.
DIP-SW
Setting
check
SW No.
Setting
-
OFF
SW2-9
(Factory setting)
ON
No.62
Fan speed for air volume "Low" input
Set the fan speed setting when receiving "Low" signal from remote
controllers(e.g. remote controller of City Multi and Mr. Slim, Lossnay
simple remote controller) which have High/Low.
DIP-SW
Setting
check
SW No.
Setting
-
OFF
SW2-10
(Factory setting)
ON
PZ-61DR-E
Setting
Outdoor temp. for Pre-
check
heater output ON
Function No. Setting Data
0
-
0 ˚C or less
(Factory setting)
-
1
-1 ˚C or less
-
2
-2 ˚C or less
-
3
-3 ˚C or less
59
-
4
-4 ˚C or less
-
5
-5 ˚C or less
-
6
-6 ˚C or less
-
7
-7 ˚C or less
PZ-61DR-E
Setting
Pre-heater output OFF
check
interval
Function No. Setting Data
0
-
1 hr
(Factory setting)
-
1
2 hrs
60
-
2
3 hrs
-
3
4 hrs
-
4
5 hrs
PZ-61DR-E
Setting
Operating fan speed
check
Function No. Setting Data
0
-
DIP-SW priority
(Factory setting)
61
1
Fan speed 4
2
Fan speed 3
PZ-61DR-E
Setting
Operating fan speed
check
Function No. Setting Data
0
-
DIP-SW priority
(Factory setting)
62
1
Fan speed 2
2
Fan speed 1