Function settings (continued)
Exhaust fan setting at OA temperature
No.14
lower than -15 ˚C
Sets the operation of the exhaust fan when the outdoor air is lower
than -15 ˚C (when supply fan stop).
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
5-3 OFF
5-9 ON
5-3 ON
SW5-3
5-9 OFF
14
SW5-9
5-3 OFF
5-9 OFF
(Factory setting)
5-3 ON
5-9 ON
* In case Lossnay is operating fan speed 1, exhaust fan keeps fan
speed 1. Function
No. 13
and
then it is impossible to set independently without PZ-61DR-E.
No.15
Interlock mode setting
These settings indicate how Lossnay should operate when external
devices are started or stopped.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
5-7 OFF
5-8 OFF
(Factory setting)
5-7 ON
5-8 OFF
SW5-7
15
SW5-8
5-7 OFF
5-8 ON
5-7 ON
5-8 ON
No.28
Pulse input setting
Set external input signal type from external device for TM2.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
OFF
SW2-2
28
(Factory setting)
ON
Eng-16
Setting
Exhaust fan operation at
check
outdoor temp. -15 ˚C or less
0
DIP-SW priority
(Factory setting)
1
Stop
Forced to fan speed 2
2
or less*
3
No change
No. 14
are included in DIP-SW 5-3,
Setting
Interlock setting
check
0
DIP-SW priority
(Factory setting)
The Lossnay will start and stop
according to the operation of the
external devices. Subsequent
1
operation will be possible using
the remote controller for the
Lossnay or MELANS.
The Lossnay will start whenever
external devices are operated.
2
Lossnay stop operation will
be possible using its remote
controller or MELANS.
The Lossnay will stop whenever
external devices are stopped.
3
Lossnay start operation will
be possible using its remote
controller or MELANS.
The Lossnay will start and stop
according to the operation of
the external devices. Control
4
via the Lossnay remote
controller or MELANS will only
be possible when external
devices are stopped.
Setting
Pulse input setting
check
0
DIP-SW priority
(Factory setting)
1
NOT pulse input
2
Pulse input
Night-purge setting 1)
No.30
Air volume
Set fan speed during Night-purge. To use Night-purge function, it is
necessary to set
No. 30
,
No. 31
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
N/A
30
-
-
-
-
-
-
Night-purge setting 2)
No.31
Outdoor and indoor temperature gap
Set one of conditions for Night-purge start, temperature gap between
indoor and outdoor.
When the actual gap between indoor and outdoor becomes bigger
than the setting, Night-purge starts.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
N/A
31
-
-
-
-
-
-
-
-
Night-purge setting 3)
No.32
Threshold of outdoor temperature
Set one of conditions for Night-purge start, maximum outdoor
temperature within the last setting hours at function
When this setting temperature is low, it is likely to start Night-purge.
This function is N/A from Lossnay unit DIP-SW.
DIP-SW
PZ-61DR-E
Setting
check
SW No.
Setting
Function No. Setting Data
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
N/A
32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
,
No. 32
correctly.
Setting
Night-purge setting 1)
check
Air volume
N/A (Night-purge
0
(Factory setting)
function is not available)
1
Fan speed 1
2
Fan speed 2
3
Fan speed 3
4
Fan speed 4
Setting
Indoor temperature -
check
outdoor temperature
0
0 ˚C or more
1
1 ˚C or more
2
2 ˚C or more
3
3 ˚C or more
4
4 ˚C or more
5
5 ˚C or more
(Factory setting)
6
6 ˚C or more
7
7 ˚C or more
No.33
.
The maximum outdoor
Setting
temp. within the last setting
check
hours at function
0
15 ˚C or more
1
16 ˚C or more
2
17 ˚C or more
(Factory setting)
3
18 ˚C or more
4
19 ˚C or more
5
20 ˚C or more
6
21 ˚C or more
7
22 ˚C or more
8
23 ˚C or more
9
24 ˚C or more
10
25 ˚C or more
11
26 ˚C or more
12
27 ˚C or more
13
28 ˚C or more
14
29 ˚C or more
15
30 ˚C or more
No.33