Installation and network integration of a CS141
1. Initial configuration
On delivery, the IP address is 10.10.10.10 and the
CS141 is in manual mode. As soon as you assign
an IP address, the CS141 will take over the new
settings without reboot:
1.
Leave the sliding switch in the left
For the CS141 MINI, keep the DIP Switch set-
tings:
DIP 1 is ON and DIP 2 is OFF.
2. Connect the CS141 to the LAN port of your work-
station via, either directly or via a switch.
When the IP address is wrong, it is possible to fall
back to the hard coded IP address 10.10.10.10 by
setting the sliding switch to center position and
rebooting the device. For CS141 MINI, put both
DIP switches to OFF and reboot the device.
2.
Connecting the UPS
... when using an external CS141
Use the original serial cable to connect
1 of the CS141
to the RS232 interface of the UPS.
... when using a CS141 Slot card
Insert the CS141 diectly into the according card
slot of the UPS. You do not need to depower the
UPS.
3. Powering up the CS141
... when using an external CS141
Connect the power adapter coming with the
CS141 device. As soon as power is available, the
CS141 will start booting
... when using a CS141 slot card
The CS141 slot card will be powered by the inter-
nal connectors of the slot provided by your UP. As
soon as you plug in the slot card, it will power up
and start booting.
Initial IP address: 10.10.10.10
position.
Slider to left position,
DIP 1 is ON
Hard coded IP address 10.10.10.10:
Slider to CENTER position
DIP 1and 2: OFF
External CS141
COM port
Slot card
Ethernet
Cable
Switch
Connect the UPS via RS232 / RS485
Insert card into the slot
External CS 141: connect power adapter
EU: 230V AC / 12 V DC