Menu Description - Allmatic BIOS2 ECO Guía Para La Instalación

Ocultar thumbs Ver también para BIOS2 ECO:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

6.3 Menu description:

6.3.1 Base settings menu
tCL Auto reclosing time
Active when the gate is in the completely open position, the gate automatically closes after tCL seconds. In this phase the display shows
with the blinking dash, that during the last 10 seconds will be replaced by the count down.
ttr Auto reclosing time after transit
If in the opening phase or in the completely open position the beam of the photocells is obscured and freed, the gate automatically closes after ttr
seconds when the completely open position is reached, In this phase the display shows
seconds will be replaced by the count down.
Trq Motor torque
Adjust the motor torque to ensure a correct functioning of the gate, it is possible to adjust the percentage of torque between 10% to 100%. After the
adjustement of this parameter it is recommended to perform a complete movimentation (opening and closing) to ensure a correct functioning of the
gate.
SSL Slowing down mode
The control unit has 2 different type of slowing downs : standard or with higher torque and speed, for heavier gates.
SbS Step by step configuration (SS)
SbS = 0 Normal (OP-ST-CL-ST-OP-ST...)
Typical functioning of Step by Step. During the movement a SS command stops the gate.
SbS = 1 Alternated STOP (OP-ST-CL-OP-ST-CL...)
Alternated functioning with STOP during the opening. During the opening phase a SS command stops the gate.
SbS = 2 Alternated (OP-CL-OP-CL...)
The user cannot stop the gate during the movement with a SS command.
A SS command during the movement inverts the movement.
SbS = 3 Condominium – timer
A SS command only opens the gate. When the gate is completely open, if the command persist the control unit will wait until the opening of
the contact before beginning the contdown of the automatic reclosing (if enabled), onother SS command in this phase will restart the contdown
of the automatic reclosing.
SbS = 4 Condominium with immediate auto reclosing
SSt Soft start
The movement begins with reduced torque, used in light gates.
dLy Second wing delay
This is the setting of the delay of the second wing to ensure a correct overlapping of the wings; the delay is the same in opening and closing. If 0 is set
the control unit will remove completely the delay. Warning overlapping of the wings.
LSI Amplitude of slowing down
With this parameter it is possible to adjust the amplitude of the slowing down and eventually disable it (LSI=0). If you need more precise or different
slowing down between opening and closing it is possible to set the parameter LSI on P (personalized) and perform an advanced learning of strokes
(5.2) providing also the beginning of slowing downs during the learning.
asL Antislip
This parameter is used if the motor slips, the control unit adds asL seconds to movimentation to ensure a complete movements of the wings also in
the worst condition.
nMt Number of motors
This parameter is used to set the number of motors, the learning operations and the functionality will be modified depending on this parameter.
6-1622176
rev. 7
18/09/2020
ITA
ENG
FRA
ESP
DEU
POR
with the blinking dash, that during the last 10
8 / 12
Tabla de contenido
loading

Tabla de contenido