6. Commissioning, operation
6.5 Parameters
Parameter
Description
SP1/SP2
Hysteresis function: Switch point switching output (1 or 2)
FH1/FH2
Window function: Window high switching output (1 or 2)
RP1/RP2
Hysteresis function: Reset point switching output (1 or 2)
FL1/FL2
Window function: Window low switch output (1 or 2)
EF
Extended programming functions
RES
Return the set parameter to the factory settings
DS1/DS2
Switch delay time, which must occur without interruption before any electrical signal change
occurs (SP1 or SP2)
DR1/DR2
Switch delay time, which must occur without interruption before any electrical signal change
occurs (RP1 or RP2)
OU1
Switching function switching output (1 or 2)
OU2
HNO = hysteresis function, normally open
HNC = hysteresis function, normally closed
FNO = window function, normally open
FNC = window function, normally closed
UNIT
Changing units
SETR
Measuring range scaling (analogue output)
"4 mA" or "0 V" determines at which temperature the output signal is to be 4 mA or 0 V.
"20 mA" or "10 V" determines at which temperature the output signal is to be 20 mA or 10 V.
OFS
Offset adjustment (3 % of span)
DISM
Display value in display mode
ACT = Actual temperature value; LOW, HIGH = Minimum, Maximum temperature value OFF =
display off;
SP1/FH1 = function switch point 1, RP1/FL1 = function reset point 1,
SP2/FH2 = function switch point 2, RP2/FL2 = function reset point 2
DISR
Rotate display indicator by 180°
RHL
Clear the Min- and Max-value memories
PAS
Password input, 0000 = no password; Password input digit by digit
TAG
Input of a 16-figure alphanumeric measuring point number
WIKA operating instructions temperature switch, model TSD-30
EN
23