Manual del usuario
Indoor Unit Register List
One Indoor unit has the following list of points. Some points may not be supported depending on the product.
Point
Description
1
On/Off
2
Swing
3
Lock
4
Mode Lock
5
Fan Lock
6
Temp Lock
7
Alarm
1
Operation Mode
2
Fan Speed
3
Set Room Temperature
4
Set Upper Temperature
5
Set Lower Temperature
6
Room Temperature
7
Error Code
8
Accumulated Power(LOW)
9
Accumulated Power(HIGH)
10
Accumulated Gas(LOW)
11
Accumulated Gas(HIGH)
Function Code
Unit
Text-0
01/05
-
Stop (0)
01/05
-
Stop (0)
01/05
-
Permit (0)
01/05
-
Permit (0)
01/05
-
Permit (0)
01/05
-
Permit (0)
01
-
Normal (0)
03/06
-
-
03/06
-
-
03/06
℃
03/06
℃
03/06
℃
03
℃
03
-
03
-
Accumulated Power Value(100 Watt) = Accumulated Power(HIGH) X 65536 + Accumulated Power(LOW)
03
-
03
-
03
-
Text-1
Text-2
Start (1)
Start (1)
Prohibit (1)
Prohibit (1)
Prohibit (1)
Prohibit (1)
Abnormal (1)
Cool (1)
Dry (2)
Low (1)
Middle (2)
16 ℃ ~ 30 ℃ (60 ℉ ~ 86 ℉)
18 ℃ ~ 30 ℃ (64 ℉ ~ 86 ℉)
16 ℃ ~ 30 ℃ (60 ℉ ~ 86 ℉)
Please refer to LG error code list.
Accumulated Gas Value(100 Liter) = Accumulated Gas(HIGH) X 65536 + Accumulated Gas(LOW)
Text-3
Text-4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Fan (3)
Auto (4)
High (3)
Auto (4)
Text-5
Text-6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Heat (5)
-
-
-