General Object List
This is the list of BACnet objects provided for the general information. Some points may not be supported depending on the product.
Point
Description
1
All Unit Run/Stop (Setting)
2
All Unit Set Room Temperature (Setting)
3
All Unit Temperature Lock (Setting)
4
Total Accumulated Power (Status)
5
Peak Control Operation (Setting)
6
Peak Control Operation (Status)
7
Peak Shift Time(Setting)
8
Peak Shift Time(Status)
9
Peak Target Ratio(Setting)
10
Peak Target Ratio(Status)
11
Peak Current Running Ratio(Status)
12
Remote Shutdown(Setting)
13
Temperature Unit Setting (Setting)
14
Temperature Unit Setting (Status)
Object
Object Name(_XXX : Address)
AllStartStopCommand
AllSetRoomTempCommand
AllTempLockCommand
TotalAccumulatedPower
PeakStartStopCommand
PeakStartStopStatus
PeakShiftTimeCommand
PeakShiftTimeStatus
PeakTargetCommand
PeakTargetStatus
PeakCurrentStatus
RemoteShutDownCommand
TempUnitCommand
TempUnitStatus
Unit
Text-0
Type
BO
-
Stop (0)
AV
℃(℉)
BO
-
Permit (0)
Prohibit (1)
AI
100 Watt
BO
-
Stop (0)
BI
-
Stop (0)
AV
min
AI
min
AV
%
AI
%
AI
%
BO
-
Normal (0)
Shutdown (1)
BO
-
℃ (0)
BI
-
℃ (0)
Text-1
Text-2
Text-3
Text-4
Start (1)
-
-
-
18 ℃ ~ 30 ℃ (64 ℉ ~ 86 ℉)
-
-
-
Wattage values
Start (1)
-
-
-
Start (1)
-
-
-
5 min ~ 15 min
5 min ~ 15 min
0 % ~ 100 %
0 % ~ 100 %
0 % ~ 100 %
-
-
-
℉ (1)
-
-
-
℉ (1)
-
-
-
Text-5
Text-6
-
-
-
-
-
-
-
-
-
-
-
-
-
-