3.6 Adjusting air when lighting a fire
-
Primary air inlet
It is essential to open this inlet to maximum position when lighting the fire and to leave the door ajar to avoid
the condensation of fumes on the glass.
Wait until the appliance has warmed up before adjusting the air inlet.
-
Secondary air inlet
Open fully when lighting a fire.
Warning. – During the use of your stove or inset appliance, the high temperatures generated during
combustion and cooling down of the device afterwards will cause expansion and contraction of the steel plates. This
may cause some metallic sounds; these are completely normal and should not be considered a defect in the product.
3.7 Regulating during operation
-
Primary air inlet
During normal operation of the burner, once the appliance has warmed up, you must close the primary air
inlet to achieve good combustion performance.
If the quality of the firewood so allows, the primary air inlet must be fully closed or slightly open (no more
than 1 cm).
PRIMARY AIR REGULATION LEVER POSITION FOR NOMINAL POWER, OPENED 25% OF ITS RANGE 10mm.
-
Secondary air inlet
Secondary air adjustment is the one that will provide better combustion that is cleaner and more efficient,
making the most of every load of firewood.
You can adjust the entry of secondary air when the apparatus is hot enough and burning with a good flame.
During normal operation, you must never close the secondary air inlet completely. Normally, the secondary
air must be adjusted to a minimum opening of 15-20%.
SECONDARY AIR REGULATION LEVER POSITION FOR NOMINAL POWER, OPENED 50% OF ITS RANGE.
28