SIMPLIFIED INSTRUCTIONS FOR SUPER 2200 FCE-FCM WITH S1-CRX
1° Connecting the motor and limit switch (done in the factory)
FCE
NO
NO
NC
NC
C
C
BLUE
CAPACITOR
BROWN
BLUE
M
BLACK
MOTOR
3 - Installing and adjusting the limit switch cams for SUPER
2200 FCM
Position the cams at the ends of the
rack rail.
Tighten the two screws to secure
them in place.
LIMIT SWITCH ADJUSTMENT FOR SUPER 2200 FCE
Release the operator using handle "A" as indicated below,
therefore releasing the G nuts.
Move the mobile part manually to establish the direction of the H
cams' movement both in opening and closing.
With the gate open and closed, put the two F limit switches on
the P handles so that they are pressed by the H cams.
Lock the G nuts.
TO OPEN THE GATE MANUALLY
The sump with the appropriate key must be opened.
Insert the RIB hex key in the release screw and turn it 3 times
anti-clockwise.
To restore the electric functioning, operate in the opposite
direction.
N.B. The H cams must press the electric micro switches before
the mobile part touches the mechanical stops.
A+A- Observe the polarity of the
photocells' electrical supply
A* A S
C NC
1
3
4
2
5
Without Edge, jumper COM-EDGE
SUPER 2200 FCM
IMPORTANT
The motor is set to open towards the right.
If opening is to the left, the LSO and LSC wires on terminal block J3 and the V
and W wires on terminal block J2 must be reversed.
2° Connecting the accessories
A* A S
SUPER 2200 FCE
ANTENNA – Use an RG58 co-axial cable