Manual Operation - Resol Solex Manual De Instrucciones

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

SOLEX
5.11
Antifreeze heat exchanger
Options/He-Frost.
Adjustment range no...yes
Factory setting yes
5.12
Afterheating
Options/afterhtg
Adjustment range no...R4+R5
Factory setting no
expert/adj.values/S1-AH
Adjustment range 1 ... 6
Factory setting 3
expert/adj.values/S2-AH
Adjustment range 1 ... 6
Factory setting 5
expert/adj.values/type-Ah
Adjustment range therm. ... boiler
Factory setting therm
adj. values/t-ah on
Adjustment range 0 ... 90°C
Factory setting 45°C
adj. values/t-ah off
Adjustment range 0 ... 90°C
Factory setting 55°C
adj. values/WT Afterheating
5.13
Balance values
Balance values
5.14

Manual operation

Manual Operation
Adjustment range Off,Auto, On
Factory setting Auto
If the feed flow temperature (T-FL) at the heat exchanger
underruns 10°C, the secondary circuit (P2) is put into ope-
ration with a minimum rotational speed in order to pro-
tect the heat exhcanger from freezing (this function can be
switched off).
The type of the afterheating function can be selected in the
expert menu.
Thermostat
Thermal afterheating is effected by a sensor and can be
selected in the expert menu. If the switch-on temperature
is underrun, the relay is switched on. If the switch-off tem-
perature is exceeded, the relay is switched off again.
Boiler
If the measured temperatures at the two temperatu-
re sensors underrun the set
T-AH ON, the relay is switched on. It is swiched off again if
the temperature at both sensors has exceeded T-AH OFF.
If one of the sensors is defective, the afterheating will be
stopped or suppressed.
Additionally, this option can be temporary locked by means
of a week timer.
Following values are balanced:
- days of operation controller
- hours of operation solar pump (P1)
- hours of operation charge pump(P2)
- hours of operation layer valve
- maxiumum temperature collector
- maximum temperature feed flow (T-FL)
- maximum temperature return flow(T-RT)
The balance values can be set back. As soon as a balance
channel is chosen, symbol SET will be permanently shown
on the display. Button SET (3) has to be pressed for approx.
2 sec. in order to get to the RESET mode. The display
symbol SET is blinking and the balance value will be set to
0. In order to finish the RESET process button SET has to
be pressed. In order to cancel the RESET process, don't
press any button at all for approx 5 sec. The controller is
automatically set to the display mode.
Each relay can be optionally set to Off- / On- or Auto-
matic mode.
switch-on temperature
29 |
Tabla de contenido
loading

Tabla de contenido