1.27 Manual Start-up

Before starting the generator set for the first time, thor-
oughly review the pre-start-up checklist in the previous
section. Proceed with generator start-up only after check-
ing each item in that section.
Thoroughly read and make sure you understand the
engine Operator's Manual supplied with the generator.
Follow the steps below and the illustration on the oppo-
site page in the order listed.
WARNING
Before placing the Engine Start Switch
"REMOTE START" position, verify that the con-
tacts on any remote switch linked to the generator
set are OPEN. If the contacts on a remote switch are
closed, the generator will crank and start when the
Engine Start Switch is moved to the "REMOTE
START" position.
WARNING
When using the generator as a standby or substitute
power supply, make sure the voltage and phase
rotation of the line connections match those of the
utility lines or of any other power source normally
used. Failure to match phase rotation and volt-
age may cause equipment connected to the gen-
erator to operate incorrectly! This could create
unsafe operating conditions.
1. Check position of Voltage Selector Switch
make sure it is set for the desired voltage output.
Lock the switch be in place.
2. Make sure the Engine Start Switch
position.
3. Turn main line circuit breaker
receptacle circuit breakers to off "O". This will discon-
nect all loads from the generator.
4. Move Engine Start Switch
to check operation of engine control module. The
LCD panel should momentarily display "SYSTEM
OK" followed by "UNIT IN AUTO" and engine
information. Check fuel level and battery values.
Note: The amber Warning Light
the fuel level is below 25%, or engine temperature is
below 70° F. This will not prevent the engine from
starting.
1A-24
All manuals and user guides at all-guides.com
(e)
in the
(a)
and
(e)
is in the off "O"
(c)
and convenience
(e)
to "REMOTE START"
(d)
will come on if
a
208
120
480
240
277
120
208
120
480
240
277
120
NEVER CHANGE SWITCH POSITION WITH ENGINE RUNNING.
RESULTS IN ELECTRIC SHOCK AND DAMAGE TO MACHINE.
..
NIEMALS SCHALTER UMSTELLEN WENN MOTOR LAUFT.
..
VERURSACHT ELEKTRISCHEN SCHLAG UND BESCHADIGUNG
..
DES GERATES.
NUNCA CAMBIE LA POSICION DEL INTERRUPTOR AL ESTAR
MARCHANDO EL MOTOR. YA QUE ESTO PODRIA CONDUCIR A
~~~
UNA DESCARGA ELECTRICA Y DANOS EN EL EQUIPO.
NE JAMAIS CHANGER LA POSITION DE L'INTERRUPTEUR
PENDANT QUE LE MOTEUR EST EN MARCHE. IL POURRAIT
EN RESULTER RISQUE D'ELECTROCUTION ET DOMMAGES
A LA MACHINE.
1026SD77
5. Press in the Emergency Stop Button
panel should read "EMERGENCY STOP", and the
(g)
red LEDs
should light up. Release the stop button
after verifying the display and the LED, and return the
Engine Start Switch to off "O".
6. Start engine by moving the Engine Start Switch to
the "RUN/START" position.
The LCD display will read "STARTING ENGINE" as
the engine begins its crank cycle. The normal cycle
is for the engine to crank for 15 seconds, then rest for
10 seconds. This cycle will repeat three (3) times. If
the engine does not start within this time, the Engine
Control Module will shut down the engine and "FAULT
OVERCRANK" will be displayed on the LCD panel.
To repeat crank cycle, return start switch to off "O" to
reset Engine Control Module. Allow starter motor to
cool between start-up attempts.
G50/G70/G85
b
1026SD84
(b)
. The LCD