4.2 Start/stop of pump
The pump can be started/stopped in two different
ways:
• Locally on the pump control panel.
• By means of an external on/off switch connected
to the start/stop input. See connection overview in
section 3.6.
4.3 Priming/venting of pump
The pump control panel incorporates a
Press this button if the maximum pump capacity is
required over a short period, e.g. during start-up.
When the button is released, the pump automatically
returns to the previous operating mode.
During priming/venting, it is recommended to let the
pump run without a counter pressure or to loosen the
vent valve by giving it a 1/8 to 1/4 turn.
NOTE: When the buttons
simultaneously, the pump can be set to run for a spe-
cific number of seconds at maximum capacity. The
remaining number of seconds will appear in the dis-
play. The maximum value is 300 seconds.
4.4 Level control
The pump can be fitted with a level control unit for
monitoring of the chemical level in the tank.
The pump can react to two level signals. The pump
will react differently, depending on the influence on
the individual level sensors.
Level sensors
Pump reaction
• Red indicator light is on.
Upper sensor
activated
• Pump running.
(closed contact)
• Alarm relay activated.*
• Red indicator light is on.
Lower sensor
activated
• Pump stopped.
(closed contact)
• Alarm relay activated.*
* Control variant "AR" only.
See section 3.6 for connection of the level control
unit and alarm output.
4.5 Indicator lights and alarm output
The green and red indicator lights on the pump are
used for operating and fault indication.
In control variant "AR", the pump can activate an
external alarm signal by means of a built-in alarm
relay. The alarm signal is activated by means of an
internal potential-free contact.
button.
100%
and
are pressed
100%
The functions of the indicator lights and the built-in
alarm relay appear from the table below:
Green
Condition
LED
LED
Pump
On
running
Flash-
Set to stop
ing
Pump fault
Off
Supply
Off
failure
Pump run-
ning, low
On
chemical
2
level
Empty
Off
2
tank
Analog
signal
Off
< 2 mA
The dosed
quantity is
too small
according
On
to the sig-
nal from
the dosing
3
monitor
Overheat-
Off
ing
1
Control variant AR only.
2
Requires connection to level sensors.
3
Requires activation of the dosing monitoring
function and connection to a dosing monitor.
Red
Alarm
Display
output
Normal
Off
indication
1
2
NC NO C
Normal
Off
indication
1
2
NC NO C
On
EEPROM
1 2
NC NO C
Off
Off
1
2
NC NO C
Normal
On
indication
1 2
NC NO C
Normal
On
indication
1 2
NC NO C
Normal
On
indication
1 2
NC NO C
Normal
On
indication
1 2
NC NO C
MAX.
On
TEMP.
1 2
NC NO C
1
3
3
3
3
3
3
3
3
3
11