Statement 7002-Intra-Building Lightning Surge (For Shielded Cables); Statement 7003-Telcordia Gr-1089 Nebs Standard For Electromagnetic Compatibility And Safety; Statement 7004-Special Accessories; Statement 7005-Intrabuilding Lightning Surge And Ac Power Fault - Cisco Catalyst 9500 Serie Manual Del Usuario

Tabla de contenido
Statement 7002—Intra-Building Lightning Surge (For Shielded
Cables)
Shielded (screened) cables utilized for connection to intra-building telecommunication ports shall be grounded
at both ends of the cable.
Statement 7003—Telcordia GR-1089 NEBS Standard for
Electromagnetic Compatibility and Safety
The intrabuilding port(s) of the equipment or subassembly must use shielded intrabuilding cabling/wiring that is
Warning
grounded at both ends.
Statement 7004—Special Accessories
To comply with emission and immunity requirements, shielded cable is required for connection to Ethernet
Ports.
Statement 7005—Intrabuilding Lightning Surge and AC Power
Fault
Warning
The intrabuilding port(s) of the equipment or subassembly must not be metallically connected to interfaces that
connect to the OSP or its wiring. These interfaces are designed for use as intrabuilding interfaces only (Type 2 or
Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed OSP cabling. The addition of
Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP wiring.
Statement 7012—Equipment Interfacing with AC Power Ports
This equipment shall be connected to AC mains provided with a surge protective device (SPD) at the service
equipment complying with NFPA 70, the National Electrical Code (NEC).
Regulatory Compliance and Safety Information—Cisco Catalyst 9500 Series Switches
12
Regulatory Compliance and Safety Information—Cisco Catalyst 9500 Series Switches